5-8
T60 Transformer Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2PRODUCT SETUP
5.2.1 SECURITY
a) SECURITY OVERVIEW
The following security features are available:
•
Password security — Basic security present in the default offering of the product
•
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
•
CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
Changing the password, or any other setting, does not take the relay out of service. The relay is taken out of service when
a settings file is written to it.
LOST PASSWORD
If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default
values, not just the passwords.
To reset the unit after a lost password:
1.
Email GE customer service at [email protected] with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2.
Enter the reset code on the front panel, under
COMMANDS
RELAY MAINTENANCE
SERVICE COMMAND
.
3.
Change the default password of ChangeMe1# as outlined in the
Setting Up CyberSentry and Changing Default Pass-
word
section in the first chapter.
PASSWORD REQUIREMENTS
A user account requires an alpha-numeric password that meets the following requirements:
•
Password is case-sensitive
•
Password cannot contain the user account name or parts of the user account that exceed two consecutive characters
•
Password must be 6 to 20 characters in length
•
Password must contain characters from three of the following four categories:
- English uppercase characters (A through Z)
- English lowercase characters (a through z)
- Base 10 digits (0 through 9)
- Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
b) PASSWORD SECURITY
PATH: SETTINGS
PRODUCT SETUP
SECURITY
The T60 supports password entry from a local or remote connection.
SECURITY
ACCESS LEVEL:
Restricted
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
MESSAGE
CHANGE LOCAL
PASSWORDS
MESSAGE
ACCESS
SUPERVISION
MESSAGE
DUAL PERMISSION
SECURITY ACCESS
MESSAGE
PASSWORD ACCESS
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...