5-156
T35 Transformer Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
5.7.6 MONITORING ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
b) BREAKER ARCING CURRENT
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER 1(6) ARCING CURRENT
MONITORING
ELEMENTS
BREAKER 1
ARCING CURRENT
See below.
MESSAGE
BREAKER 2
ARCING CURRENT
MESSAGE
BREAKER 3
ARCING CURRENT
MESSAGE
BREAKER 4
ARCING CURRENT
MESSAGE
BREAKER 5
ARCING CURRENT
MESSAGE
BREAKER 6
ARCING CURRENT
MESSAGE
CT FAILURE
DETECTOR
MESSAGE
THERMAL OVERLOAD
PROTECTION
BREAKER 1
ARCING CURRENT
BKR 1 ARC AMP
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BKR 1 ARC AMP
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
BKR 1 ARC AMP INT-A:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 ARC AMP INT-B:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 ARC AMP INT-C:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 ARC AMP
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BKR 1 ARC AMP LIMIT:
1000 kA2-cyc
Range: 0 to 50000 kA
2
-cycle in steps of 1
MESSAGE
BKR 1 ARC AMP BLOCK:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 ARC AMP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BKR 1 ARC AMP
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...