5-16
T35 Transformer Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
•
In Local Authentication mode, the Observer role does not have a password associated with it. In Remote Authentica-
tion mode the Observer role requires a password.
•
The default password is “ChangeMe1#”.
•
Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.
•
In CyberSentry, password encryption is not supported.
d) SESSION SETTINGS
PATH: SETTINGS
PRODUCT SETUP
SECURITY
SESSION SETTINGS
The following session settings are available.
•
SESSION LOCKOUT
: This setting specifies the number of failed authentications (the default is three and the maxi-
mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero means
lockout is disabled.
•
SESSION LOCKOUT PERIOD
: This setting specifies the period of time in minutes of a lockout period (the default is
three and the maximum is 9999). A value of 0 means that there is no lockout period.
e) RESTORE DEFAULTS
PATH: SETTINGS
PRODUCT SETUP
SECURITY
RESTORE DEFAULTS
•
LOAD FACTORY DEFAULTS
: This setting is used to reset all the settings, communication and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
f) SUPERVISORY
PATH: SETTINGS
PRODUCT SETUP
SECURITY
SUPERVISORY
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
MESSAGE
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No
SUPERVISORY
LOCAL
AUTHENTICATION:Yes
Range: Yes, No
MESSAGE
BYPASS ACCESS:
Disabled
Range: Enabled, Disabled
MESSAGE
LOCK RELAY:
Disabled
Range: Enabled, Disabled
MESSAGE
FACTORY SERVICE:
MODE: Disabled
Range: Enabled, Disabled
MESSAGE
SELF TESTS
See below
MESSAGE
SUPERVISOR ROLE:
Disabled
Range: Enabled, Disabled
MESSAGE
SERIAL INACTIVITY
TIMEOUT: 1 min
Range: 1 to 9999 minutes
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...