Chapter 4
– Configuration
RPV311
82
RPV311-TM-EN-7
B
The T
ERMINAL
text field allows user to enter the terminal of this recorder.
C
The T
RIGGER
LOGIC
field contains all the thresholds created. The logic equation uses
AND and OR logic operators over previously defined thresholds. Initially, all preset
thresholds are displayed as implicit OR operators, one per line.
To enable thresholds individually, click on the threshold and select Enable;
To disable discarded thresholds individually, click on the threshold and select Disable;
To break or remove complex thresholds, click on the threshold and select Cut last;
To create equations with AND operators, follow the procedures below:
Click on the threshold and select Cut last;
Click on the threshold to which is desired to add the previously selected
threshold and then select the threshold to be added.
D
Selecting the R
ECEIVE
E
THERNET
CROSS
-
TRIGGER
or S
END
E
THERNET CROSS
-
TRIGGER
check
box enables these features. It allows the start of the recording of an exceeded
threshold by Ethernet cross-trigger.
Note:
The maximum number of RA333 that can be connected to the RPV311 is 4.
The RA333 module has to be connected to the RPV311 processing module before its
initianilzaton. Otherwise a log message will tell the user to reboot the device.
13
Recommended Sources of Trigger
In order to register the beginning of the fault’s traveling wave it is important to use
instantaneous protections trips (or starts) as digital input for trigger, for example: 50,
21Z1, 67I, 87 etc. In addition, we recommend the following thresholds:
Threshold
Limit
Phase Overcurrent
1,2 pu
Neutral Overcurrent
0,2 pu
Current Negative Sequence 0,15 pu
Phase Undervoltage
0,85 pu
Neutral Overvoltage
0,10 pu
The limits values can be adjusted depending on the needs of each installation using
real events as basis
14
Steady-State
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...