![GE RPV311 Technical Manual Download Page 54](http://html.mh-extra.com/html/ge/rpv311/rpv311_technical-manual_133552054.webp)
Chapter 4
– Configuration
RPV311
54
RPV311-TM-EN-7
Figure 13: Analog inputs configuration section
A
The P
OSITION
indicates the position of each analog input on the back panel of the
module.
B
The I
NPUT
scroll box allows user to select the type of the signal to be measured (AC
voltage 115 V, AC current 1 A, AC current 5 A, DC current 0-20 mA or DC voltage ±10
V).
C
The A
DJUSTMENT
text field allows user to enter a correction factor to adjust the
accuracy of the measurement.
2.5
Acquisition with Sampled Values
The RPV311 data acquisition can be performed by Sampled Values data, incoming of
Merging Units. The acquisition is done by connecting the Process Bus Ethernet port to
the Sampled Values generator.
If the acquisition is done by Sampled Values, there is no physical link to configure.
The configuration is performed by Subscription links. Each subscription link contains
data of 4 current (Phases A, B, C and Neutral) and 4 voltage (Phases A, B, C and
Neutral) circuits.
Once a subscription link is created, the RPV311 automatically configures the first
channels as current and the last as voltage, as shown in Figure 86. This is done
because the Merging Units send the Sampled Values package according to the IEC
61850-9-2LE.
The RPV311 processing module can be configured with up to 8 Subscription links.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...