RPV311
Chapter 3
– Hardware Design
36
RPV311-TM-EN-7
1.1
Processing Capability
The RPV311 has 8 link connections to communicate with RA33x acquisition units. As
each acquisition unit has different number of channels and functions, they require
different levels of demand from the RPV311. In order to respect the RPV311
processing capability the number of RA33x that can be connected to the RPV311
obey the following rule:
The RPV311 can process 12 logical slots and each RA demands the following number
of slots.
The user can combine the RA units as long as the logical sum of the slots value of
each RA do not exceed the maximum number of 12.
Note:
Differently from the RA331/332 the RA333 has two link: One for the DFR
functionality and another for the TW functionality.
2
Mechanical Implementation
2.1
RPV311
2.1.1
Main features
Fan-less and no rotating part design
Trigger waveform recorder at 256, 128, or 64 points-per-cycle;
Continuous waveform recorder at 16 points-per-cycle;
Continuous disturbance recorder and trigger recorder (optional);
Trigger using Boolean logic equations;
Traveling wave recorder for fault location (optional);
MODBUS and DNP3 interface for SCADA integration (optional);
Synchrophasor measurement according to IEEE C37.118 (optional);
Power quality records:
Device
Logic Demand (slots)
RA331
1
RA332
2
RA333 DFR
1
RA333 TW
2
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...