![GE RPV311 Technical Manual Download Page 35](http://html.mh-extra.com/html/ge/rpv311/rpv311_technical-manual_133552035.webp)
RPV311
Distributed Multifunction Fault Recorder
Chapter 3: Hardware Design
This chapter provides information about the hardware design of the products.
1
Hardware Architecture
The RPV311 is a multifunction processing unit and has an acquisition system with 16-
bit A/D D converters that provide an acquisition rate of 256 points-per-cycle
synchronized by the IRIG-B signal.
It has a high processing capability, which allows the acquisition of up to 64 analog
channels and 256 digital channels divided in up to 8 acquisition modules connected
by fiber-optic links. Additionally, it is able to detect IEC 61850 GOOSE messages.
All the registers are stored in a SSD hard disk.
It allows communication through the electrical Ethernet ports and optionally has a
double internal converter for optical Ethernet interfaces.
Monitoring and configuration are performed through a web interface; also, it has a
human-machine interface on the front panel for displaying information. It has a
MODBUS and DNP3 interface for SCADA integration.
The RA331 module allows data acquisition of up to 8 analog channels (voltage,
current, or DC transducers) and up to 32 digital channels. The RA332 module allows
data acquisition of up to 16 analog channels (voltage, current, or DC transducers)
and up to 32 digital channels. Both modules use 16-bit A/D converters providing an
acquisition rate of 256 points-per-cycle.
The RA333 module allows data acquisition of high-speed analog channels (voltage)
for one transmission line. This module allows the scheme to obtain traveling wave
records for fault locating. Additionally, the RA333 module allows data acquisition of
up to 8 analog channels (voltage, current, or DC transducers) and up to 32 digital
channels, using 16-bit A/D converters providing an acquisition rate of 256 points-per-
cycle
Figure 2: RA332, RA333 and RPV311
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...