RPV311
Distributed Multifunction Fault Recorder
Chapter 8: PMU
This chapter provides detailed information about the PMU feature.
1
Synchrophasor Measurement and Broadcast
Synchrophasors are measured and broadcast according to the specifications
contained in IEEE C37.118, Standard for Synchrophasors for Power Systems.
1.1
Reported Values
The reported values are user-selectable of the list below.
Reported values user-selectable
Phasors
Voltage synchrophasors (any phase)
Current synchrophasors (any phase)
Positive and Negative sequence for voltage
circuits
Positive and Negative sequence for current
circuits
Frequency
Frequency and frequency variation of one circuit
Scalars
Any DC channel
Voltage (RMS) value (any phase)
Current (RMS) value (any phase)
Voltage circuit imbalance
Current circuit imbalance
Total voltage harmonic distortion (any phase)
Total current harmonic distortion (any phase)
3-phase Apparent Power from phasor (S1) and
from RMS (S)