Chapter 9
– TW Fault Locator
RPV311
146
RPV311-TM-EN-7
The most complete test would be using two sets of RA333:
1.
Make sure that both RPV311 are properly time synced. For conditions that
are more realistic, the sync sources could be independent;
2.
Configure a line arbitrarily long on the RPV Manager or TW Fault Locator
software connecting the two sets of equipment;
3.
Configure the TW register to be triggered by an undervoltage threshold in
both RPV311;
4.
Connect three phase voltage to the TW analogic inputs in both RPV311
though a circuit-breaker or test switch;
5.
Switch off the circuit-breaker (or test switch), both RA333 should indicate the
BUSY state, showing that the TW is being processed. register is being
processed;
6.
Download both files to a computer with the TW Fault Locator tool installed.
7.
Run the TW Fault Locator tool to find the fault location (Procedure described
RPV311 manual, in topic 14.5). The fault location should be 50% of the line.
Alternatively, it is possible to useone RPV311 and two RA333 connected to the same
RPV311. Taking care when creating the powerline file, in which only the “line”
parameter will be different, for example:
<terminal_a>LOCATION,IDENTIFIER,LINE_A</terminal_a>
<terminal_b>LOCATION,IDENTIFIER,LINE_B</terminal_b>
Another possibility that also tests the acquisition system of the RA333 module, is to
use only one RA333 and configure the powerline file with the same
parameters for both terminals, for example:
<terminal_a>LOCATION,IDENTIFIER,LINE_A</terminal_a>
<terminal_b>LOCATION,IDENTIFIER,LINE_A</terminal_b>
In this case, the TW fault locator tool will use the same file for both ends locating the
fault.
For all the previous mentioned tests, the algorithm shall point the fault location at
50% of the line length, as we are using with very short cable lengths or using the
same TW register for both ends.
5
Three Terminal Line Application
The figure below shows a line of three-terminal. The Terminal A, B and C (sources X, Y
and Z respectively).
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...