Chapter 9
– TW Fault Locator
RPV311
144
RPV311-TM-EN-7
The RPV from one terminal does not need to communicate with the other terminal’s
RPV in order to create the TW COMTRADE file.
A communication link is only needed between the control centers and the RPVs (or
local data concentrators) the user wants to implement remote access to the
equipment.
The communication setup that the user would deploy to download the TW record
and perform the fault location is exactly the same as the one used to download the
fault records.
The fault distance is calculated based on the time that each wavefront arrived at the
line terminal. According to the following equation.
𝑑 =
𝑙 + 𝐾𝑐(𝑡
𝑎
− 𝑡
𝑏
)
2
Where:
d:
fault distance from terminal A;
l:
length of the line;
k:
constant of the line attenuation of the speed of the wave;
c:
speed of light
t
a:
time which the traveling wave gets to terminal A
t
b
:
time which the traveling wave gets to terminal B
The means to get the COMTRADE files from the RPV311 to the computer where the
fault location will be performed are described in Chapter 5: Operation, COMTRADE
files download.
The TW record is a COMTRADE file with 100ms prior to the trigger plus 1 cycle after
the trigger, that means approximately 117 ms @ 60 Hz and 120 ms @ 50 Hz. The
RPV311 takes 2 minutes to create a record and during that time the device stays in a
“BUSY” status and will not record a new TW record until the BUSY status is finished.
2
TW Fault Location Information
2.1
Maximum Number of Lines Monitored by the TW Fault
Locator
If the voltage is sourced from a bus VT you only need one RA333 to capture TWs from
all the lines connected to that bus, however simultaneous or consecutive faults (less
than 2 minutes apart) on lines connected to that bus will not be captured.. Moreover,
it is possible to connect up to 4 modules RA333 to one processing unit RPV311.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...