Chapter 6: Records
This chapter details all types of registers created by the RPV311.
1
Continuous and Triggered Fault Records
Fault records can be created in the following ways:
Continuously:
Measurements are continuously recorded. A new record is available each 10
minutes. The record size depends on the number of derived measurements selected
by the user (limited to 16).
By trigger:
The fault recorder can be triggered by a Boolean equation, by a cross-trigger signal
of another recorder or by a manual trigger using the Web Interface.
Continuous and triggered fault records share the same mass storage area.
1.1
Recorded Values
The following values are recorded by the fault recorder:
Voltage waveform of all voltage circuits (A, B, C, and N);
Current waveform of all current circuits (A, B, C, and N);
Transducer waveform of all transducer channels;
Digital channels (state of digital inputs and binary GOOSE messages).
1.2
Recording Times by Trigger
Once triggered, the following parameters are considered by the fault recorder:
Parameter
Allowed values
Increment
Pre-fault time (
𝑡
pre
)
0 … 5 s
0.1 s
Post-fault time (
𝑡
pos
)
0 … 60 s
0.1 s
Maximum Record
time (
𝑡
max
)
1 … 60 s
0.1 s
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...