Appendix C IC755CxS12CDA Serial Port
Details
•
A terminal block is supplied.
•
The mating terminal block supports stranded 30-14 AWG (0.05 – 2.00 mm
2
) wires.
•
At a minimum, the cable must be rated for 75°C (167 °F) or more.
•
Secure the serial cable to the mating connector while noting signal orientation and
tighten the screw clamps.
•
The torque for the attaching screws is 0.3 Nm (2.66 in-lb).
Interface: x1 RS–232, x1 RS-232/485 (default is RS-485)
Connectors: Euro Terminal (Tyco Electronics 1-284539-0)
Mating Connector: (Tyco Electronics 1-284510-0)
Pin #
Signal Name
Pin-out
COM1
10
1
1
TXD
2
RXD
3
RTS
4
CTS
5
SGND
COM2 (RS-232/485
†
)
6
TXD/TXD+/DATA+
7
RXD/TXD-/DATA-
8
RTS/RXD+/DATA+
9
CTS/RXD-/DATA-
10
SG
†
RS-485 mode shorts pins 6-8 and 7-9