4–18
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 4: SOFTWARE
FIGURE 4–5: Data Logger Window
5.
The Data Log 1(2) dialog box displays the record numbers, data log start time,
the current time, and parameter values for the current cursor line position.
4.5.5
Voltage Disturbance Recorder
The Voltage Disturbance Recorder allows the PQMII to monitor and record sag and swell
disturbances. This function can record up to 500 sag/swell events for all voltages
simultaneously. The events roll-over and old events are lost when more than 500 events
are recorded.
Note
PQMII VDR events are stored in volatile memory. Therefore, all voltage disturbance
events will be cleared when control power is cycled to the meter.
The operation of the voltage disturbance recorder as implemented in the EnerVista PQMII
Setup Software is shown below:
Z
Select the
Setpoint > System Setup > System Config
menu item.
Z
Select the
Voltage Disturbance Recorder
Setup tab.
Z
The
Sag Level % Nominal
should be set to the level to which a voltage
input must fall before a sag event is to be recorded. The
Swell
Level % Nominal
should be set to the level to which a voltage input
must rise before a swell event is to be recorded.
Z
Click
Save
to send the current settings to the PQMII.
Summary of Contents for PQM II
Page 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Page 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Page 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Page 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Page 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Page 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Page 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...