Chapter 3. Installation and Start-up: Rack-based and RX7i Embedded Interface
GFK-2224Q
January 2017
29
Direct Connection to the PACSystems Ethernet Interface
Connection of Ethernet devices directly to the Ethernet Interface is shown below:
10/100
10/100
10BaseT/100Base Tx
Twisted Pair Cable
Other Ethernet
devices such as PCs,
Ethernet Interfaces
on other PLCs,
Operator Interfaces
Ethernet
Interface
Figure 12: Direct Connection to the Embedded Ethernet Ports
3.4
Station Manager Port
The RX7i and rack-based RX3i Ethernet interfaces provide a dedicated RS-232 serial port for local Station
Manager use. This nine-pin D connector accepts a standard straight-through nine-pin RS-232 serial cable to
connect to a standard AT-style RS-232 port.
The following cable is available:
IC200CBL001
Cable, CPU Programming
Port Settings
The serial (COM) port of the terminal or computer that is connected to the Ethernet Interface must use the
same communications parameters as the Ethernet Interface.
The default values for the Station Manager port are 9600 bps, 8 bits, no parity, and 1 stop bit. If the Ethernet
Interface is configured with default values for this port, or the Ethernet Interface has not been configured, use
these default values. If the Ethernet Interface is configured with non-default values for this port, use those
values for the serial port settings of the terminal or computer.
Summary of Contents for PACSystems RX7i
Page 45: ......
Page 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Page 81: ......
Page 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Page 147: ......
Page 211: ......
Page 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Page 263: ......