Chapter 11. RX7i PLC Monitoring Via the Web
202
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
PLC Fault Table Viewer Page
The PLC Fault Table Viewer displays the contents of the PLC fault table.
The PLC name is shown at the top of the page, together with the PLC timestamp showing when the page was
accessed or refreshed.
The PLC fault table provides up to 16 entries arranged from newest to oldest. If there are fewer than 16 entries,
the remaining rows are blank. If there are more than 16 faults, the table displays the most recent faults in the
first 8 rows and the oldest faults in the last 8 rows.
To change the format of the fault extra data, select the appropriate checkbox at the top of the page.
To refresh the fault data, click the ‘Refresh PLC Fault Table’ button.
When using Internet Explorer, the fault extra data can be viewed by using the mouse to highlight a particular
fault and then clicking on the fault. This is shown below:
Figure 85: PLC Fault Table Display
The fault extra data can be displayed in byte, word or ASCII format depending on which button is selected at
the top of the screen. These selections affect the display of all fault extra data. If an error code does not have
a string associated with it, the “Fault Description” field is blank.