Chapter 5. PLC Hardware Configuration (Primary PLC)
GFK-2928
December 2017
25
5.4
Configure the PROFINET Controller Module
The PROFINET Controller Module has a 32-bit diagnostic/status reference. The recommended starting
reference is %I16465 (the next available reference following the Ethernet port status reference).
Figure 23: Assign PROFINET Status Address
NOTE 1
: For each slot in which a PROFINET Controller is installed, the Primary module and the
Secondary module will always have identical Status Addresses. (However, the PROFINET
Controllers from one slot to another will have separate, unique addresses).
NOTE 2
: For the purposes of early project development/debug, it may be simpler to disable the
port criticality parameters. However, these should be enabled before the project is
installed in an operating environment.
Figure 24: Disable Port Criticality (for Debug only)