![GE PACSystems RSTi-EP Cpu Programmer'S Reference Manual Download Page 415](http://html.mh-extra.com/html/ge/pacsystems-rsti-ep/pacsystems-rsti-ep_cpu-programmers-reference-manual_123065415.webp)
Chapter 9. Diagnostics
400
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
GFK-2950C
9.4.5
Reset of, Addition of, or Extra Option Module (Group 8)
The fault group Reset of, Addition of, or Extra Option Module occurs when an option module (LAN
interface module, BTM, etc.) comes online, is reset, is hot inserted or a module is found in the rack
but is not configured.
Action: Non-configurable.
3, LAN Interface Restart Complete, Running Utility
The LAN Interface module has restarted and is running a utility program.
Correction
Refer to the LAN Interface manual, GFK-0868 or GFK-0869 (previously GFK-0533).
7, Extra Option Module
Note:
This fault is logged for an RX3i CPE310 that is configured as a CPU310, or a CPE330
configured as a CPU320, because the RX3i system detects the embedded Ethernet module
as an unconfigured module.
Correction
1)
Update the configuration file to include the module.
2)
Remove the module from the system.
E Hex/14 Decimal, Option Module Hot inserted
The CPU logs this fault when it detects hot insertion of an option module such as the LAN interface
module. No correction necessary
Note:
When configuration is cleared or stored, a reset fault is generated for every intelligent option
module physically present in the system.
Summary of Contents for PACSystems RSTi-EP
Page 357: ......
Page 466: ...Chapter 9 Diagnostics GFK 2950C February 2018 451 ...