
2
THERMAL OVERLOAD PROTECTION
Transformer overheating can be caused due to failures of the cooling system, external faults that are not cleared
promptly, or overload and abnormal system conditions. These abnormal conditions include low frequency, high
voltage, non-sinusoidal load current, or phase-voltage imbalance.
Overheating shortens the life of the transformer insulation in proportion to the duration and magnitude of the high
temperature. If excessive, this may even result in an immediate insulation failure. Overheating can also generate
gases that could result in electrical failure, or cause the transformer coolant to be heated above its flashpoint
temperature, introducing the risk of fire.
Studies suggest that the life of insulation is approximately halved for each 10°C rise in temperature above the
rated value. However, the life of insulation is not wholly dependent on the rise in temperature but on the time the
insulation is subjected to this elevated temperature. Due to the relatively large heat storage capacity of a
transformer, infrequent overloads of short duration may not damage it. However, sustained overloads of a few
percent may result in premature aging and consequent insulation failure.
Transformer thermal overload protection is designed to protect equipment from sustained overload. Thermal
overload protection allows modest but transient overload conditions to occur, while tripping for sustained
overloads, which would not be detected by standard overcurrent protection.
Transformer Losses
The losses in a transformer are shown in the following diagram:
V03200
Transformer Losses
Load Losses
No Load Losses
Copper Losses
Eddy-current Losses
Hysteresis Losses
Stray Losses
Apparent Losses
Core Losses
(Iron Losses)
Figure 62: Transformer losses
The flow of the magnetising current through the resistance of the winding creates a real but generally relatively
small I
2
R loss and voltage drop. The loss that is due to this magnetizing current in the primary winding is called the
apparent loss.
Time-varying fluxes in iron-based materials, cause losses called core losses, or iron losses. These iron losses are
divided into two categories; hysteresis losses and eddy-current losses.
The sum of copper losses and the stray losses is called the load loss. Copper losses are due to the flow of load
currents through the primary and secondary windings. They are equal to I
2
R, and they heat up the wires and
cause voltage drops. Stray losses are due to the stray capacitance and leakage inductance. Stray capacitance
exists between turns, between one winding and another, and between windings and the core.
2.1
THERMAL OVERLOAD IMPLEMENTATION
The thermal overload protection in this device is based on the IEEE Standard C57.91-1995. It provides thermal
overload protection for either an individual winding or the transformer as a whole. The thermal overload
protection settings are in the THERMAL OVERLOAD column.
Chapter 7 - Transformer Condition Monitoring
P64x
144
P64x-TM-EN-1.3
Summary of Contents for P642
Page 2: ......
Page 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Page 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Page 25: ...CHAPTER 1 INTRODUCTION ...
Page 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Page 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Page 37: ...CHAPTER 2 SAFETY INFORMATION ...
Page 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Page 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Page 51: ...CHAPTER 3 HARDWARE DESIGN ...
Page 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Page 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Page 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Page 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Page 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Page 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Page 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Page 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Page 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Page 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Page 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Page 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Page 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Page 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Page 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Page 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Page 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Page 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Page 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Page 307: ...CHAPTER 14 SUPERVISION ...
Page 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Page 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Page 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Page 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Page 337: ...CHAPTER 16 COMMUNICATIONS ...
Page 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Page 397: ...CHAPTER 17 CYBER SECURITY ...
Page 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Page 415: ...CHAPTER 18 INSTALLATION ...
Page 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Page 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Page 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Page 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Page 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Page 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Page 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Page 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Page 507: ...APPENDIX A ORDERING OPTIONS ...
Page 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Page 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Page 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 515: ...APPENDIX C WIRING DIAGRAMS ...
Page 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Page 590: ......
Page 591: ......