
2
TRANSFORMER DIFFERENTIAL PROTECTION PRINCIPLES
Transformer Differential Protection (87T) uses the well-known current differential principle where current entering
the protected equipment is compared with the current leaving the protected equipment. If there is no fault, the
current entering the transformer will be equal to the current leaving the transformer multiplied by the inverse of
the turns ratio. If there is a fault in the transformer zone, the currents will not be equal, which results in a
differential current. This differential current is proportional to the fault current for internal faults, but approaches
zero for any other operating conditions. The IED trips the circuit breakers protecting the transformer when it
detects a minimum level of differential current.
The differential scheme creates a well-defined protection zone between the CT sets protecting the transformer.
Any fault within the differential protection zone is called an internal fault, while any fault outside the differential
protection zone is called an external fault. The protection should operate only for internal faults and be sensitive to
low fault currents. It should also restrain on the highest prospective external faults, providing the CTS accurately
reproduce the primary currents. This is difficult to achieve in practice because the CTs never have identical
saturation characteristics. This will result in a differential current, which could cause undesirable operation.
An external fault, which causes a high current to flow through the transformer, is called a through fault. The
through-fault current will usually be high enough to saturate the CTs. The differences in the saturation
characteristics of the CTs will cause a differential current, which could cause the device to trip unless it is
restrained. The term used to specify the IED's ability to cope with these imperfections is called Through Fault
Stability.
CT saturation is not the only cause of undesirable differential current. Other aspects which need to be considered
by the transformer differential element to avoid maloperation are:
●
Phase shift between the transformer primary and secondary currents depending on the vector group
●
Transformation ratio
●
The zero-sequence current, which flows in the grounded star transformer winding or the grounding
transformer within the differential protection zone
●
Tap changer operation to adjust the voltage
●
Magnetising inrush current that flows immediately after the transformer energisation or during a voltage
recovery after the clearance of an external fault or when a second transformer is paralleled with the
already energised transformer
●
Over excitation of the transformer
2.1
THROUGH FAULT STABILITY
In an ideal world, the CTs either side of a differentially protected system would be identical with identical
characteristics to avoid creating a differential current. However, in reality CTs can never be identical, therefore a
certain amount of differential current is inevitable. As the through-fault current in the primary increases, the
discrepancies introduced by imperfectly matched CTs is magnified, causing the differential current to build up.
Eventually, the value of the differential current reaches the pickup current threshold, causing the protection
element to trip. In such cases, the differential scheme is said to have lost stability. To specify a differential scheme’s
ability to restrain from tripping on external faults, we define a parameter called ‘through-fault stability limit’, which
is the maximum through-fault current a system can handle without losing stability.
2.2
BIAS CURRENT COMPENSATION
To prevent maloperation, compensation is needed for the protection to remain sensitive to internal faults but to
ignore through faults. This is achieved by applying a proportion of the scalar sum of all the currents entering and
exiting the zone. This scalar sum is called bias current.
The bias characteristic changes the operating point of the IED depending on the fault current. At low through-fault
currents, the CT performance is more reliable so a low bias current is needed. Less differential current is then
needed to trip the circuit breakers, allowing greater sensitivity to internal faults. At high through-fault currents, the
Chapter 6 - Transformer Differential Protection
P64x
100
P64x-TM-EN-1.3
Summary of Contents for P642
Page 2: ......
Page 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Page 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Page 25: ...CHAPTER 1 INTRODUCTION ...
Page 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Page 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Page 37: ...CHAPTER 2 SAFETY INFORMATION ...
Page 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Page 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Page 51: ...CHAPTER 3 HARDWARE DESIGN ...
Page 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Page 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Page 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Page 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Page 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Page 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Page 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Page 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Page 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Page 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Page 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Page 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Page 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Page 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Page 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Page 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Page 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Page 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Page 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Page 307: ...CHAPTER 14 SUPERVISION ...
Page 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Page 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Page 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Page 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Page 337: ...CHAPTER 16 COMMUNICATIONS ...
Page 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Page 397: ...CHAPTER 17 CYBER SECURITY ...
Page 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Page 415: ...CHAPTER 18 INSTALLATION ...
Page 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Page 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Page 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Page 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Page 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Page 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Page 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Page 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Page 507: ...APPENDIX A ORDERING OPTIONS ...
Page 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Page 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Page 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 515: ...APPENDIX C WIRING DIAGRAMS ...
Page 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Page 590: ......
Page 591: ......