RESIDUAL OVERVOLTAGE PROTECTION
On a healthy three-phase power system, the sum of the three-phase to earth voltages is nominally zero, as it is the
vector sum of three balanced vectors displaced from each other by 120°. However, when an earth fault occurs on
the primary system, this balance is upset and a residual voltage is produced. This condition causes a rise in the
neutral voltage with respect to earth. Consequently this type of protection is also commonly referred to as 'Neutral
Voltage Displacement' or NVD for short.
This residual voltage may be derived (from the phase voltages) or measured (from a measurement class open
delta VT). Derived values will normally only be used where the model does not support measured functionality (a
dedicated measurement class VT). If a measurement class VT is used to produce a measured Residual Voltage, it
cannot be used for other features such as Check Synchronisation.
This offers an alternative means of earth fault detection, which does not require any measurement of current. This
may be particularly advantageous in high impedance earthed or insulated systems, where the provision of core
balanced current transformers on each feeder may be either impractical, or uneconomic, or for providing earth
fault protection for devices with no current transformers.
4.1
RESIDUAL OVERVOLTAGE PROTECTION IMPLEMENTATION
Residual Overvoltage Protection is implemented in the RESIDUAL O/V NVD column of the relevant settings group.
Some applications require more than one stage. For example an insulated system may require an alarm stage and
a trip stage. It is common in such a case for the system to be designed to withstand the associated healthy phase
overvoltages for a number of hours following an earth fault. In such applications, an alarm is generated soon after
the condition is detected, which serves to indicate the presence of an earth fault on the system. This gives time for
system operators to locate and isolate the fault. The second stage of the protection can issue a trip signal if the
fault condition persists.
The product provides two stages of Residual Overvoltage protection with independent time delay characteristics.
Stage 1 provides a choice of operate characteristics, where you can select between:
●
An IDMT characteristic
●
DT (Definite Time)
The IDMT characteristic is defined by the following formula:
t = K/( M - 1)
where:
●
K= Time multiplier setting
●
t = Operating time in seconds
●
M = Derived residual voltage setting voltage (VN> Voltage Set)
You set this using the VN>1 Function setting.
Stage 1 also provides a Timer Hold facility.
Stage 2 can have definite time characteristics only. This is set in the VN>2 status cell
The device derives the residual voltage internally from the three-phase voltage inputs supplied from either a 5-limb
VT or three single-phase VTs. These types of VT design provide a path for the residual flux and consequently permit
the device to derive the required residual voltage. In addition, the primary star point of the VT must be earthed.
Three-limb VTs have no path for residual flux and are therefore unsuitable for this type of protection.
Chapter 11 - Voltage Protection Functions
P64x
244
P64x-TM-EN-1.3
Summary of Contents for P642
Page 2: ......
Page 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Page 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Page 25: ...CHAPTER 1 INTRODUCTION ...
Page 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Page 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Page 37: ...CHAPTER 2 SAFETY INFORMATION ...
Page 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Page 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Page 51: ...CHAPTER 3 HARDWARE DESIGN ...
Page 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Page 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Page 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Page 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Page 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Page 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Page 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Page 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Page 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Page 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Page 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Page 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Page 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Page 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Page 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Page 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Page 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Page 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Page 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Page 307: ...CHAPTER 14 SUPERVISION ...
Page 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Page 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Page 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Page 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Page 337: ...CHAPTER 16 COMMUNICATIONS ...
Page 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Page 397: ...CHAPTER 17 CYBER SECURITY ...
Page 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Page 415: ...CHAPTER 18 INSTALLATION ...
Page 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Page 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Page 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Page 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Page 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Page 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Page 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Page 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Page 507: ...APPENDIX A ORDERING OPTIONS ...
Page 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Page 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Page 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 515: ...APPENDIX C WIRING DIAGRAMS ...
Page 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Page 590: ......
Page 591: ......