3.2
ZERO CROSSING DETECTION
When there is a fault and the circuit breaker interrupts the CT primary current, the flux in the CT core decays to a
residual level. This decaying flux introduces a decaying DC current in the CT secondary circuit known as
subsidence current. The closer the CT is to its saturation point, the higher the subsidence current.
The time constant of this subsidence current depends on the CT secondary circuit time constant and it is generally
long. If the protection clears the fault, the CB Fail function should reset fast to avoid maloperation due to the
subsidence current. To compensate for this the device includes a zero-crossing detection algorithm, which ensures
that the CB Fail re-trip and back-trip signals are not asserted while subsidence current is flowing. If all the samples
within half a cycle are greater than or smaller than 0 A (10 mS for a 50 Hz system), then zero crossing detection is
asserted, thereby blocking the operation of the CB Fail function. The zero-crossing detection algorithm is used
after the circuit breaker in the primary system has opened ensuring that the only current flowing in the AC
secondary circuit is the subsidence current.
This zero-crossing detection algorithm considers the current inputs T1, T2, T3, T4 and T5 on a per phase basis. If
IN< Input is set as
measured
, the zero crossing detection algorithm considers the current inputs TN1, TN2 and
TN3. If IN< Input is set as
derived
, the zero crossing detection algorithm considers the current inputs T1, T2, T3,
T4 and T5. If more than 12 consecutive samples are greater than 0A or more than 12 consecutive samples are
smaller than 0A, then a zero crossing detection condition is asserted, which blocks the operation of the circuit
breaker failure function. The zero crossing detection is asserted after the breaker in the primary system has
opened to ensure that the current flowing in the AC secondary circuit is just the subsidence current.
Chapter 10 - CB Fail Protection
P64x
230
P64x-TM-EN-1.3
Summary of Contents for P642
Page 2: ......
Page 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Page 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Page 25: ...CHAPTER 1 INTRODUCTION ...
Page 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Page 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Page 37: ...CHAPTER 2 SAFETY INFORMATION ...
Page 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Page 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Page 51: ...CHAPTER 3 HARDWARE DESIGN ...
Page 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Page 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Page 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Page 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Page 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Page 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Page 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Page 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Page 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Page 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Page 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Page 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Page 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Page 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Page 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Page 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Page 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Page 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Page 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Page 307: ...CHAPTER 14 SUPERVISION ...
Page 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Page 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Page 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Page 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Page 337: ...CHAPTER 16 COMMUNICATIONS ...
Page 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Page 397: ...CHAPTER 17 CYBER SECURITY ...
Page 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Page 415: ...CHAPTER 18 INSTALLATION ...
Page 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Page 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Page 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Page 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Page 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Page 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Page 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Page 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Page 507: ...APPENDIX A ORDERING OPTIONS ...
Page 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Page 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Page 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 515: ...APPENDIX C WIRING DIAGRAMS ...
Page 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Page 590: ......
Page 591: ......