3.2
APPLICATION NOTES
3.2.1
LOL SETTING GUIDELINES
Set the life hours at the reference maximum Hotspot temperature. According to IEEE Std. C57.91-1995, the normal
insulation life at the reference temperature in hours or years must be user-defined. The following table extracted
from IEEE Std. C57.91-1995 gives values of normal insulation life for a well-dried, oxygen-free 65°C average
winding temperature rise insulation system at the reference temperature of 110°C.
Basis
Normal Insulation life Hours
Normal Insulation Life Years
50% retained tensile strength of insulation (former IEEE Std
C57.92-1981 criterion)
65000
7.42
25% retained tensile strength of insulation
135000
15.41
200 retained degree of polymerization in insulation
150000
17.12
Interpretation of distribution transformer functional life test
data (former IEEE Std. C57.91-1981)
180000
20.55
Note:
Tensile strength or degree of polymerization (D.P.) retention values were determined by sealed tube aging on well-dried
insulation samples in oxygen-free oil.
Note:
Refer to I.2 in annex I of the IEEE Std. C57.91-1995 for discussion of the effect of higher values of water and oxygen and also
for the discussion on the basis given above.
You should set the designed Hotspot temperature setting (Designed HS temp) to 110°C if the transformer is rated
65°C average winding rise. If the transformer is rated 55°C average winding rise, set it to 95°C.
As recommended by IEEE C57.91-1995, set the Constant B Set setting to 5000.
If the calculated aging acceleration factor is greater than the setting FAA> Set and the time delay tFAA> Set has
elapsed, the FAA alarm DDB signal is activated.
If the calculated loss of life is greater than the setting LOL>1 Set and the time delay tLOL> Set has elapsed, the
LOL alarm DDB signal is activated.
3.2.2
EXAMPLE
Consider a new 65°C average winding rise rated transformer whose life hours figure at designed maximum
Hotspot temperature is 180,000 hrs. As a result, you set the Life Hours at HS setting to
180,000
, and the
Designed HS temp setting to 110.0°C. Set Constant B Set to
15,000
as recommended by IEEE. The aging
acceleration factor takes into consideration the constant B and the hottest spot temperature calculated by the
thermal function. For a distribution transformer, IEEE suggests 200°C as the limit for the maximum hot spot
temperature. The aging acceleration factor alarm will be asserted when 70% of the 200°C has been reached. The
aging acceleration factor is calculated as follows:
FAA
e
e
B
B
hottest spot tempt
B
B
=
=
−
−
−
+
−
×
+
383
273
383 0 7 200 273
.
=
17 2
.
Therefore:
FAA>set should be set to
17.2
. tFAA> Set may be set to
10.00 min
. LOL>1 Set may be set to
115,000 hrs
, if
it is considered that the transformer has 65,000 hrs left (Life Hours at HS – hours left = 180,000 – 65,000 = 115,000
hrs). tLOL> Set may be set to
10.00 min
. Finally, the Reset Life Hours setting determines the value of the LOL
Chapter 7 - Transformer Condition Monitoring
P64x
152
P64x-TM-EN-1.3
Summary of Contents for P642
Page 2: ......
Page 18: ...Contents P64x xvi P64x TM EN 1 3 ...
Page 24: ...Table of Figures P64x xxii P64x TM EN 1 3 ...
Page 25: ...CHAPTER 1 INTRODUCTION ...
Page 26: ...Chapter 1 Introduction P64x 2 P64x TM EN 1 3 ...
Page 36: ...Chapter 1 Introduction P64x 12 P64x TM EN 1 3 ...
Page 37: ...CHAPTER 2 SAFETY INFORMATION ...
Page 38: ...Chapter 2 Safety Information P64x 14 P64x TM EN 1 3 ...
Page 50: ...Chapter 2 Safety Information P64x 26 P64x TM EN 1 3 ...
Page 51: ...CHAPTER 3 HARDWARE DESIGN ...
Page 52: ...Chapter 3 Hardware Design P64x 28 P64x TM EN 1 3 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P64x 64 P64x TM EN 1 3 ...
Page 98: ...Chapter 4 Software Design P64x 74 P64x TM EN 1 3 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P64x 76 P64x TM EN 1 3 ...
Page 121: ...CHAPTER 6 TRANSFORMER DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Transformer Differential Protection P64x 98 P64x TM EN 1 3 ...
Page 165: ...CHAPTER 7 TRANSFORMER CONDITION MONITORING ...
Page 166: ...Chapter 7 Transformer Condition Monitoring P64x 142 P64x TM EN 1 3 ...
Page 189: ...CHAPTER 8 RESTRICTED EARTH FAULT PROTECTION ...
Page 190: ...Chapter 8 Restricted Earth Fault Protection P64x 166 P64x TM EN 1 3 ...
Page 215: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 216: ...Chapter 9 Current Protection Functions P64x 192 P64x TM EN 1 3 ...
Page 249: ...CHAPTER 10 CB FAIL PROTECTION ...
Page 250: ...Chapter 10 CB Fail Protection P64x 226 P64x TM EN 1 3 ...
Page 259: ...CHAPTER 11 VOLTAGE PROTECTION FUNCTIONS ...
Page 260: ...Chapter 11 Voltage Protection Functions P64x 236 P64x TM EN 1 3 ...
Page 274: ...Chapter 11 Voltage Protection Functions P64x 250 P64x TM EN 1 3 ...
Page 275: ...CHAPTER 12 FREQUENCY PROTECTION FUNCTIONS ...
Page 276: ...Chapter 12 Frequency Protection Functions P64x 252 P64x TM EN 1 3 ...
Page 286: ...Chapter 12 Frequency Protection Functions P64x 262 P64x TM EN 1 3 ...
Page 287: ...CHAPTER 13 MONITORING AND CONTROL ...
Page 288: ...Chapter 13 Monitoring and Control P64x 264 P64x TM EN 1 3 ...
Page 306: ...Chapter 13 Monitoring and Control P64x 282 P64x TM EN 1 3 ...
Page 307: ...CHAPTER 14 SUPERVISION ...
Page 308: ...Chapter 14 Supervision P64x 284 P64x TM EN 1 3 ...
Page 322: ...Chapter 14 Supervision P64x 298 P64x TM EN 1 3 ...
Page 323: ...CHAPTER 15 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 15 Digital I O and PSL Configuration P64x 300 P64x TM EN 1 3 ...
Page 336: ...Chapter 15 Digital I O and PSL Configuration P64x 312 P64x TM EN 1 3 ...
Page 337: ...CHAPTER 16 COMMUNICATIONS ...
Page 338: ...Chapter 16 Communications P64x 314 P64x TM EN 1 3 ...
Page 397: ...CHAPTER 17 CYBER SECURITY ...
Page 398: ...Chapter 17 Cyber Security P64x 374 P64x TM EN 1 3 ...
Page 415: ...CHAPTER 18 INSTALLATION ...
Page 416: ...Chapter 18 Installation P64x 392 P64x TM EN 1 3 ...
Page 431: ...CHAPTER 19 COMMISSIONING INSTRUCTIONS ...
Page 432: ...Chapter 19 Commissioning Instructions P64x 408 P64x TM EN 1 3 ...
Page 460: ...Chapter 19 Commissioning Instructions P64x 436 P64x TM EN 1 3 ...
Page 461: ...CHAPTER 20 MAINTENANCE AND TROUBLESHOOTING ...
Page 462: ...Chapter 20 Maintenance and Troubleshooting P64x 438 P64x TM EN 1 3 ...
Page 477: ...CHAPTER 21 TECHNICAL SPECIFICATIONS ...
Page 478: ...Chapter 21 Technical Specifications P64x 454 P64x TM EN 1 3 ...
Page 507: ...APPENDIX A ORDERING OPTIONS ...
Page 508: ...Appendix A Ordering Options P64x P64x TM EN 1 3 ...
Page 512: ...Appendix A Ordering Options P64x A4 P64x TM EN 1 3 ...
Page 513: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 515: ...APPENDIX C WIRING DIAGRAMS ...
Page 516: ...Appendix C Wiring Diagrams P64x P64x TM EN 1 3 ...
Page 590: ......
Page 591: ......