P54A/B/C/E
Appendix B - Settings and Signals
P54xMED-TM-EN-1
B169
MENU TEXT
COL
ROW
DEFAULT SETTING
AVAILABLE OPTIONS
DESCRIPTION
Zero sequence impedance angle of the section between J3 and J4
Y1 J3-J4
30
44
0.00000001*I1
From 0.00000001*I1 to 10*I1 in steps of
0.00000001*I1
[Courier Number (inverse ohms)]
Positive sequence admittance amplitude of the section between junction J3 and J4
Y0 J3-J4
30
45
0.00000001*I1
From 0.00000001*I1 to 10*I1 in steps of
0.00000001*I1
[Courier Number (inverse ohms)]
Zero sequence admittance amplitude of the section between junction J3 and J4
GROUP 1: CURRENT
DIFF
33
00
This column contains settings for Current Differential
Phase Diff
33
01
Enabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Differential protection function in the group.
Phase Is1
33
70
0.2*I1
From 0.1*l1 to 2*l1 in steps of 0.05*I1
[Courier Number (current)]
Defines the minimum pick-up level of the IED.
Phase Is2
33
71
2*I1
From 1*I1 to 30*I1 in steps of 0.05*I1
[Courier Number (current)]
Defines the bias current threshold, above which the higher percentage bias k2 is used
Phase K1
33
72
30
From 0 to 150 in steps of 5
[Courier Number (percentage)]
The lower percentage bias setting used when the bias current is below Is2. This provides stability for small CT mismatches, whilst ensuring
good sensitivity to resistive faults under heavy load conditions.
Phase K2
33
73
150
From 30 to 150 in steps of 5
[Courier Number (percentage)]
The higher percentage bias setting used to improve IED stability under heavy through fault current conditions.
Phase K2
33
74
100
From 30 to 150 in steps of 5
[Courier Number (percentage)]
The higher percentage bias setting used to improve IED stability under heavy through fault current conditions.
Ktransient
33
75
200
From 100 to 200 in steps of 5
[Courier Number (percentage)]
This will replace the values of k1 & k2 while the circuit breaker is changing state from open to close. The characteristic will only be used for 5
power cycles
Is1 Restrain
33
76
4
From 0 to 5 in steps of 0.01
[Courier Number (current)]
Value added to the Is1 threshold when a trasient condition is detected
Phase Time Delay
33
78
0
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the time-delay for the definite time setting if selected. The setting is visible only when DT function is selected.
PIT Time
33
7B
0.2
From 0 to 0.2 in steps of 0.005
[Courier Number (time-seconds)]
This timer is initiated upon receipt of PIT flag in the message. Once this timer elapses, and as long as the current is above of Is1 setting, the
IED closes its three phase differential trip contacts.
Ph CT Corr'tion
33
7C
1
From 1 to 8 in steps of 0.01
[Courier Number (decimal)]
Setting used to compensate CT ratios mismatch between terminals.
IbiasThreshold
33
81
4
From 0.001*I1 to 10*I1 in steps of 0.01*I1
[Courier Number (current)]
Current threshold for CT saturation module
Capacitor Comp.
33
82
Disabled
Disabled
Enabled
[Indexed String]
Enable or disable capacitor compensation.
Ph Diff Stub Bus
33
83
Disabled
Disabled
Enabled
[Indexed String]
Enable/Disable of Stub Bus Protection.
Summary of Contents for P4A
Page 2: ......
Page 20: ...Contents P54A B C E xviii P54xMED TM EN 1 ...
Page 27: ...CHAPTER 1 INTRODUCTION ...
Page 28: ...Chapter 1 Introduction P54A B C E 2 P54xMED TM EN 1 ...
Page 38: ...Chapter 1 Introduction P54A B C E 12 P54xMED TM EN 1 ...
Page 39: ...CHAPTER 2 SAFETY INFORMATION ...
Page 40: ...Chapter 2 Safety Information P54A B C E 14 P54xMED TM EN 1 ...
Page 52: ...Chapter 2 Safety Information P54A B C E 26 P54xMED TM EN 1 ...
Page 53: ...CHAPTER 3 HARDWARE DESIGN ...
Page 54: ...Chapter 3 Hardware Design P54A B C E 28 P54xMED TM EN 1 ...
Page 86: ...Chapter 3 Hardware Design P54A B C E 60 P54xMED TM EN 1 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P54A B C E 62 P54xMED TM EN 1 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P54A B C E 74 P54xMED TM EN 1 ...
Page 120: ...Chapter 5 Configuration P54A B C E 94 P54xMED TM EN 1 ...
Page 121: ...CHAPTER 6 CURRENT DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Current Differential Protection P54A B C E 96 P54xMED TM EN 1 ...
Page 149: ...CHAPTER 7 AUTORECLOSE ...
Page 150: ...Chapter 7 Autoreclose P54A B C E 124 P54xMED TM EN 1 ...
Page 207: ...CHAPTER 8 CB FAIL PROTECTION ...
Page 208: ...Chapter 8 CB Fail Protection P54A B C E 182 P54xMED TM EN 1 ...
Page 219: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 220: ...Chapter 9 Current Protection Functions P54A B C E 194 P54xMED TM EN 1 ...
Page 244: ...Chapter 9 Current Protection Functions P54A B C E 218 P54xMED TM EN 1 ...
Page 247: ...CHAPTER 10 VOLTAGE PROTECTION FUNCTIONS ...
Page 248: ...Chapter 10 Voltage Protection Functions P54A B C E 222 P54xMED TM EN 1 ...
Page 261: ...CHAPTER 11 FREQUENCY PROTECTION FUNCTIONS ...
Page 262: ...Chapter 11 Frequency Protection Functions P54A B C E 236 P54xMED TM EN 1 ...
Page 268: ...Chapter 11 Frequency Protection Functions P54A B C E 242 P54xMED TM EN 1 ...
Page 269: ...CHAPTER 12 MONITORING AND CONTROL ...
Page 270: ...Chapter 12 Monitoring and Control P54A B C E 244 P54xMED TM EN 1 ...
Page 300: ...Chapter 12 Monitoring and Control P54A B C E 274 P54xMED TM EN 1 ...
Page 301: ...CHAPTER 13 SUPERVISION ...
Page 302: ...Chapter 13 Supervision P54A B C E 276 P54xMED TM EN 1 ...
Page 312: ...Chapter 13 Supervision P54A B C E 286 P54xMED TM EN 1 ...
Page 323: ...CHAPTER 14 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 14 Digital I O and PSL Configuration P54A B C E 298 P54xMED TM EN 1 ...
Page 336: ...Chapter 14 Digital I O and PSL Configuration P54A B C E 310 P54xMED TM EN 1 ...
Page 337: ...CHAPTER 15 FIBRE TELEPROTECTION ...
Page 338: ...Chapter 15 Fibre Teleprotection P54A B C E 312 P54xMED TM EN 1 ...
Page 354: ...Chapter 15 Fibre Teleprotection P54A B C E 328 P54xMED TM EN 1 ...
Page 355: ...CHAPTER 16 ELECTRICAL TELEPROTECTION ...
Page 356: ...Chapter 16 Electrical Teleprotection P54A B C E 330 P54xMED TM EN 1 ...
Page 366: ...Chapter 16 Electrical Teleprotection P54A B C E 340 P54xMED TM EN 1 ...
Page 367: ...CHAPTER 17 COMMUNICATIONS ...
Page 368: ...Chapter 17 Communications P54A B C E 342 P54xMED TM EN 1 ...
Page 439: ...CHAPTER 18 CYBER SECURITY ...
Page 440: ...Chapter 18 Cyber Security P54A B C E 414 P54xMED TM EN 1 ...
Page 457: ...CHAPTER 19 INSTALLATION ...
Page 458: ...Chapter 19 Installation P54A B C E 432 P54xMED TM EN 1 ...
Page 471: ...CHAPTER 20 COMMISSIONING INSTRUCTIONS ...
Page 472: ...Chapter 20 Commissioning Instructions P54A B C E 446 P54xMED TM EN 1 ...
Page 513: ...CHAPTER 21 MAINTENANCE AND TROUBLESHOOTING ...
Page 514: ...Chapter 21 Maintenance and Troubleshooting P54A B C E 488 P54xMED TM EN 1 ...
Page 530: ...Chapter 21 Maintenance and Troubleshooting P54A B C E 504 P54xMED TM EN 1 ...
Page 531: ...CHAPTER 22 TECHNICAL SPECIFICATIONS ...
Page 532: ...Chapter 22 Technical Specifications P54A B C E 506 P54xMED TM EN 1 ...
Page 558: ...Chapter 22 Technical Specifications P54A B C E 532 P54xMED TM EN 1 ...
Page 559: ...APPENDIX A ORDERING OPTIONS ...
Page 560: ...Appendix A Ordering Options P54A B C E P54xMED TM EN 1 ...
Page 565: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 566: ...Appendix B Settings and Signals P54A B C E P54xMED TM EN 1 ...
Page 790: ...Appendix B Settings and Signals P54A B C E B224 P54xMED TM EN 1 ...
Page 835: ...APPENDIX C WIRING DIAGRAMS ...
Page 836: ...Appendix C Wiring Diagrams P54A B C E P54xMED TM EN 1 ...
Page 849: ......