6-6
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
STATUS
CHAPTER 6: ACTUAL VALUES
6
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.
6.3.7 Virtual outputs
ACTUAL VALUES
STATUS
VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.3.8 RxGOOSE status
ACTUAL VALUES
STATUS
RxGOOSE STATUS
The
All RxGOOSE Online
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Input.
6.3.9 RxGOOSE statistics
ACTUAL VALUES
STATUS
RxGOOSE STATISTICS
RxGOOSE 1(64)
Cont Op xx
Off
Range: On, Off, VOff, VOn, IOn, IOff
VIRTUAL OUTPUTS
Virt Op 1
Off
Range: On, Off
Virt Op 96
Off
Range: On, Off
RxGOOSE
STATUS
All RxGOOSE Online:
Yes
Range: Yes, No
RxGOOSE 1 Status:
Offline
Range: Online, Offline
RxGOOSE 64 Status:
Offline
Range: Online, Offline
The N60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
RxGOOSE 1
RxGOOSE 1
stNum: 0
Range: 0 up to 4,294,967,295
RxGOOSE 1
sqNum: 0
Range: 0 up to 4,294,967,295
R-RxGOOSE 1
IGMP: Off
Range: On, Off