5-26
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
In addition to supporting syslog, a N60 with CyberSentry also saves the security events in two local security files, these
being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in
the EnerVista software under
Maintenance > Retrieve File
. Depending on the level of criticality/severity, a syslog server or
a reporting tool gathering information from a syslog server can produce reports, charts, and so on. All severity levels are
per RFC 5424.
Table 5-6: CyberSentry system events recorded
5.3.2 Display properties
SETTINGS
PRODUCT SETUP
DISPLAY PROPERTIES
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE
— This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
Event
Severity
Description
FAILED_AUTH, ORIGIN, TIMESTAMP
Warning (4)
A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
AUTH_LOCKOUT, ORIGIN, TIMESTAMP Error (3)
An authentication lockout has occurred because of too many failed
authentication attempts
FIRMWARE_UPGD, ORIGIN,
TIMESTAMP
Warning (4)
Indicates that a change of firmware has occurred
FIRMWARE_LOCK, ORIGIN,
TIMESTAMP
Critical (1)
An attempt was made to change firmware while the firmware lock was
enabled
SETTING_CHG, ORIGIN, TIMESTAMP
Notice (5)
Indicates setting change(s)
SETTING_LOCK, ORIGIN, TIMESTAMP Critical (1)
An attempt was made to change settings while the settings lock was enabled
LOGIN, ORIGIN, TIMESTAMP
Warning (4)
Indicates when a certain role logged in
LOGOUT, ORIGIN, TIMESTAMP
Notice (5)
Indicates when a certain role logged out or timed out
CLEAR_OSCILLOGRAPHY
Notice (5)
Clear oscillography command was issued
CLEAR_DATA_LOGGER
Notice (5)
Clear data logger command was issued
CLEAR_DEMAND_RECS
Notice (5)
Clear demand records command was issued
CLEAR_ENERGY
Notice (5)
Clear energy command was issued
RESET_UNAUTH_ACCESS
Warning (4)
Reset Unauthorized access command was issued
CLEAR_TELEPROTECTION_CNT
Notice (5)
Clear teleprotection counters command was issued
CLEAR_ALL_RECS
Warning (4)
Clear all records command was issued
DISPLAY
PROPERTIES
LANGUAGE:
English
Range:
English; English, French; English, Russian; English,
Chinese; English, German (examples; depends on order code)
Visible when language other than English purchased
FLASH MESSAGE
TIME: 1.0 s
Range: 0.5 to 10.0 s in steps of 0.1
DEFAULT MESSAGE
TIMEOUT: 300 s
Range: 10 to 900 s in steps of 1
DEFAULT MESSAGE
INTENSITY: 25 %
Range: 25%, 50%, 75%, 100%
Visible when a VFD is installed
SCREEN SAVER
FEATURE: Disabled
Range: Disabled, Enabled
Visible when an LCD is installed
SCREEN SAVER WAIT
TIME: 30 min
Range: 1 to 65535 min. in steps of 1
Visible when an LCD is installed
CURRENT CUT-OFF
LEVEL: 0.020 pu
Range: 0.002 to 0.020 pu in steps of 0.001
VOLTAGE CUT-OFF
LEVEL: 1.0 V
Range: 0.1 to 1.0 V secondary in steps of 0.1