4-2
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
ENERVISTA SOFTWARE INTERFACE
CHAPTER 4: INTERFACES
4
•
Remote resources
•
Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the N60 with settings files:
Modbus Slave Address
Modbus TCP Port Number
RS485 COM2 Baud Rate
RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address
IP Subnet Mask
IP Routing
When a settings file is loaded to a N60 that is in-service, the following sequence occurs:
1.
The N60 takes itself out of service.
2.
The N60 issues a UNIT NOT PROGRAMMED major self-test error.
3.
The N60 closes the critical fail contact.
The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.
4.1.3 Event viewing
While the interface is in either online or offline mode, you can view and analyze data generated by triggered parameters,
via one of the following:
•
Event recorder
— The event recorder captures contextual data associated with the last 1024 events, listed in
chronological order from most recent to oldest
•
Oscillography
— The oscillography waveform traces and digital states are used to provide a visual display of power
system and relay operation data captured during specific triggered events
Event records are viewable at the software and device-specific level. Access the former under
Admin > Event Log > View
.
Access the latter for a device under
Actual Values > Records > Event Record
.
Event record entries are explained in the next chapter for CyberSentry. The following table outlines some software-level
entries.
Table 4-1: Event records explained
Event
Description
EnerVista UR Setup SESSION STARTED
The EnerVista software was launched
Language was changed.
The user changed the software language using the
View > Language
menu item
DEFAULT USERS CREATED
The user management window was launched using the
Admin > User Management
menu
item
: Successful upload of firmware
END
Firmware verified
Firmware uploaded
Firmware erased
START: Upload new firmware
The firmware on a device was upgraded
EnerVista UR Setup EVENT LOG CLEARED The event record was cleared. All event records were deleted using the
Admin > Event Log >
Clear
menu item.