6-13
6 COMMISSIONING
6.11 TIME OVERCURRENT (51PH, 51PL, 51N, 51G AND 46)
6
6.11 TIME OVERCURRENT (51PH, 51PL, 51N, 51G AND 46)
Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the
protection element being tested.
Apply 0.9 times the Pickup current and check that the relay does not trip.
Apply 1.5 times the Pickup current. The relay should trip according to the time corresponding to its set curve.
Apply 5 times the Pickup current. The relay should trip according to the time corresponding to its set curve.
PROTECTION ELEMENT SETTINGS (51PH, 51PL, 51N, 51G AND 46)
SETTING
VALUE
UNIT
FUNCTION
ENABLED
INPUT
PHASOR (DFT)
PICKUP LEVEL
1
A
CURVE
MODIFY FOR EACH TEST
TD MULTIPLIER
MODIFY FOR EACH TEST
VOLTAGE RESTRAINT
DISABLED
ELEMENT
PHASE
CURVE TYPE
DIAL
TIMES
IPICKUP
TRIPPING TIMES (SEC)
EXPECTED
ADMISSIBLE
51PH
IA
IEEE Ext Inv
0.5
0.9
NA
1.5
11.34
[11.00 – 11.60]
5
0.648
[0.600 – 0.710]
IB
IEC Curve A
0.05
0.9
NA
1.5
0.860
[0.750 – 0.950]
5
0.214
[0.200 – 0.300]
51PL
IC
IEEE Ext Inv
0.5
0.9
NA
1.5
11.34
[11.00 – 11.60]
5
0.648
[0.600 – 0.710]
IB
IEC Curve A
0.05
0.9
NA
1.5
0.860
[0.750 – 0.950]
5
0.214
[0.200 – 0.300]
51N
IC
IEEE Ext Inv
0.5
0.9
NA
1.5
11.34
[11.00 – 11.60]
5
0.648
[0.600 – 0.710]
51G
IG
Definite Time
2
0.9
NA
5
2.000
[1.900 – 2.100]
46
I2
IEC Curve A
0.05
0.9
NA
1.5
0.860
[0.750 – 0.950]
5
0.214
[0.200 – 0.300]
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...