GEK-113000T
F650 Digital Bay Controller
6-9
6 COMMISSIONING
6.8 INPUTS AND OUTPUTS
6
6.8INPUTS AND OUTPUTS
During all tests, the screw on the rear of the relay must be grounded.
6.8.1 DIGITAL INPUTS
During this test, the user will determine the activation/deactivation points for every input in the relay for the set voltage value
of 30 Volts.
Verify that the error does not exceed ± 10% (+10% on activation, -10% on deactivation).
Default board settings for the input test can be modified in EnerVista 650 Setup software in:
Setpoint>Inputs/Outputs>Contact I/O>Board X
X, will be substituted by the corresponding board:
F for board in first slot
G for board in second slot
H for board in first slot of CIO module
J for board in second slot of CIO module
Test settings for mixed board (type 1:16 inputs and 8 outputs):
The inputs test is completed by groups of 8 inputs, as this type of board has 2 groups of 8 inputs with the same common.
For the first 8 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 8 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC16) must also be set to POSITIVE.
Test settings for mixed board (type 2: 8 digital inputs, 4 blocks for supervision and 8 outputs):
The inputs test is completed by groups of 4 inputs, as this type of board has 2 groups of 4 inputs with the same common.
For the first 4 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 4 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC8) must also be set to POSITIVE.
If the relay incorporates more input modules, these tests must also be applied to them.
I/O BOARD TYPE 1 (MIXED)
Voltage Threshold A_X
30 V
Voltage Threshold B_X
40 V
Debounce Time A_X
5 ms
Debounce Time B_X
5 ms
Input Type_X_CC1 (CC1)
POSITIVE
...
...
Input Type_X_CC16 (CC16)
POSITIVE
I/O BOARD TYPE 2 (SUPERVISION)
Voltage Threshold A_X
30 V
Voltage Threshold B_X
40 V
Debounce Time A_X
5 ms
Debounce Time B_X
5 ms
Input Type_X_CC1 (CC1)
POSITIVE
...
...
Input Type_X_CC8 (CC8)
POSITIVE
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...