GEK-113285A
G650 Generator Protection & Control System
C-1
APPENDIX C
C.1 DNP 3.0 PROTOCOL SETTINGS
C
APPENDIX C DNP 3.0 PROTOCOL FOR G650C.1DNP 3.0 PROTOCOL SETTINGS
G650 units enable the user to program certain parameters related to DNP3 protocol. These parameters are called DNP3
protocol settings and can be modified from the front panel or from the Level 2 software. The G650 relay supports
communication with multiple masters (3) and maintains three separate groups of DNP3 settings. Each group of DNP3
settings is related to a single
logical DNP3 slave device
. The G650 relay is able to communicate simultaneously with up to
three different DNP3 master stations. Each master communicates with a different
logical DNP3 slave
, these logical slaves
appearing as separate physical DNP3 slaves. This is achieved by keeping separate set of settings, event queues and set of
states for each logical device.
Notice that it is necessary to set different
DNP Address
and
TCP/UDP Port
for each
logical DNP3 slave device
.
Time synchronization through DNP protocol is available from all three DNP masters that can communicate with G650.
However the date & time will be taken from only one master at the same moment. It is recommended to use only one
master to do time sync through DNP.
SETTING NO
SETTING NAME
DEFAULT VALUE
RANGE
1
Physical Port
NONE
NONE, COM1, COM2, NETWORK
2
Address
255
0 to 65534, step 1
3
IP Addr Client1 Oct1
0
0 to 255 step 1
4
IP Addr Client1 Oct2
0
0 to 255 step 1
5
IP Addr Client1 Oct3
0
0 to 255 step 1
6
IP Addr Client1 Oct4
0
0 to 255 step 1
7
IP Addr Client2 Oct1
0
0 to 255 step 1
8
IP Addr Client2 Oct2
0
0 to 255 step 1
9
IP Addr Client2 Oct3
0
0 to 255 step 1
10
IP Addr Client2 Oct4
0
0 to 255 step 1
11
IP Addr Client3 Oct1
0
0 to 255 step 1
12
IP Addr Client3 Oct2
0
0 to 255 step 1
13
IP Addr Client3 Oct3
0
0 to 255 step 1
14
IP Addr Client3 Oct4
0
0 to 255 step 1
15
IP Addr Client4 Oct1
0
0 to 255 step 1
16
IP Addr Client4 Oct2
0
0 to 255 step 1
17
IP Addr Client4 Oct3
0
0 to 255 step 1
18
IP Addr Client4 Oct4
0
0 to 255 step 1
19
IP Addr Client5 Oct1
0
0 to 255 step 1
20
IP Addr Client5 Oct2
0
0 to 255 step 1
21
IP Addr Client5 Oct3
0
0 to 255 step 1
22
IP Addr Client5 Oct4
0
0 to 255 step 1
23
TCP/UDP Port
20000
1 to 65535, step 1
24
Unsol Resp Function
DISABLED
DISABLED, ENABLED
25
Unsol Resp TimeOut
5 s
0 to 60 sec, step 1
26
Unsol Resp Max Ret
10
1 to 255, step 1
27
Unsol Resp Dest Adr
200
0 to 65519, step 1
28
Current Scale Factor
1
0.00001, 0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000
29
Voltage Scale Factor
1
0.00001, 0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000
30
Power Scale Factor
1
0.00001, 0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000
31
Energy Scale Factor
1
0.00001, 0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000
32
Other Scale Factor
1
0.00001, 0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000
33
Current Deadband
30000
0 to 65535, step 1
34
Voltage Deadband
30000
0 to 65535, step 1
35
Power Deadband
30000
0 to 65535, step 1
36
Energy Deadband
30000
0 to 65535, step 1
37
Other Deadband
30000
0 to 65535, step 1
38
Msg Fragment Size
240
30 to 2048, step 1
39
Binary Input Block1
CTL EVENTS 1-16
See the explanation below
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...