GEK-113285A
G650 Generator Protection & Control System
10-5
10 APPLICATION EXAMPLES
10.2 EXAMPLE 2: PROCEDURE TO SET AN OPERATION
10
10.2EXAMPLE
2
: PROCEDURE TO SET AN OPERATION
10.2.1 DESCRIPTION OF THE EXERCISE
This simple operation describes how to program and set an operation command on the G650 relay. In the present case the
operation is:
To configure some G650 output contact to be operated since the front of the relay.
To set some LED to show the operation of the output contact (while being closed).
To close a G650 output contact using a front key pushbutton.
To reset the output contact and LED using another front key pushbutton.
10.2.2 PROCEDURE
Set the following values:
Under
SETPOINT
⇓
CONTROL ELEMENTS
⇒
INPUTS/OUTPUTS
⇒
BOARD F
*
This setting is non-relevant since it applies only when “
pulse
” type is chosen
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OUTPUTS
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
LEDS
NAME
VALUE
Output Logic_00_00
Positive
Output Type_00_00
Latch
Pulse Output Time
10000ms
*
SELECT
NAME
SOURCE
Contact Output Operate 00 (Board F)
C_Output Oper_00_00
Operation_bit000
Contact Output Reset 00 (Board F)
C_Output Reset_00_00
Operation_bit001
SELECT
NAME
SOURCE
Led 14
Close Contact_00_00
C_Output_00_00
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...