GEK-113285A
G650 Generator Protection & Control System
10-1
10 APPLICATION EXAMPLES
10.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
10
10 APPLICATION EXAMPLES 10.1EXAMPLE 1: COMMUNICATION &
PROTECTION SETTINGS PROCEDURE
10.1.1 DESCRIPTION OF THE EXERCISE
The requirements for this setting exercise are:
Communicate the relay via serial cable or Ethernet 10/100 Base T cable using EnerVista 650 Setup program.
Set some Phase Time Overcurrent protection function to operate at 5A, Inverse curve IEC, Dial 0.1
Set some Output contact on board F to be operated and sealed by the operation of the phase TOC.
Set some LED to show the operation of the phase TOC
Set some Operation to reset the output contact after dropout of the phase TOC since the front F1 pushbutton.
Set some Oscillography channel to record the pickup of phase TOC and output contact closing action.
To test the operation of this Phase Time Overcurrent protection
10.1.2 PROCEDURE TO COMMUNICATE WITH THE RELAY
This procedure describes the connection between any Laptop and some G650 relay using the
EnerVista 650 SETUP
program
For any one of these connections check first the communication parameters as follows:
Serial Communication
(RS232 front port of the relay)
With the ESC key check on the main front screen the serial communication parameters (Baud rate, parity, data bits, stop bit
and ID number).
Connect the serial cable PC-G650
Open the EnerVista 650 SETUP program in the PC and under
Communication
⇓
Computer
menu check that the serial
communication parameters displayed are the same read in the front of the relay. Check also that:
Control Type is set to No Control Type
Startup Mode is set to Communicate with relay
Click
ON
key.
Ethernet LAN
(10/100 Base T rear port of the relay)
In the Laptop choose
My PC-Control Panel-Network-Protocols-Protocol TCP/IP-Advance
and set in
IP Address
screen the following:
IP Address 192.168.37.126
Netmask
255.255.255.0
In the front of G650 relay and pressing the ESC key display the
Main Settings
screen.
Move clockwise the rotating knob to choose
Change Settings
and press down the rotating knob.
Choose
Comm Settings
and press down the rotating knob.
Choose
Network 0
and press down the rotating knob. It will be displayed
IP Address OCT 1
and set it according to the
following table:
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...