GEK-113285A
G650 Generator Protection & Control System
9-13
9 COMMISSIONING
9.11 TIME OVERCURRENT (51PH, 51PL, 51N, 51G)
9
9.11 TIME OVERCURRENT (51PH, 51PL, 51N, 51G)
Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the
protection element being tested.
Apply 0.9 times the Pickup current and check that the relay does not trip.
Apply 1.5 times the Pickup current. The relay should trip according to the time corresponding to its set curve.
Apply 5 times the Pickup current. The relay should trip according to the time corresponding to its set curve.
PROTECTION ELEMENT SETTINGS (51PH, 51PL, 51N, 51G )
SETTING
VALUE
UNIT
FUNCTION
ENABLED
INPUT
PHASOR (DFT)
PICKUP LEVEL
1
A
CURVE
MODIFY FOR EACH TEST
TD MULTIPLIER
MODIFY FOR EACH TEST
VOLTAGE RESTRAINT
DISABLED
ELEMENT
PHASE
CURVE TYPE
DIAL
TIMES
IPICKUP
TRIPPING TIMES (SEC)
EXPECTED
ADMISSIBLE
51PH
IA
IEEE Ext Inv
0.5
0.9
NA
1.5
11.34
[11.00 – 11.60]
5
0.648
[0.600 – 0.710]
IB
IEC Curve A
0.05
0.9
NA
1.5
0.860
[0.750 – 0.950]
5
0.214
[0.200 – 0.300]
51PL
IC
IEEE Ext Inv
0.5
0.9
NA
1.5
11.34
[11.00 – 11.60]
5
0.648
[0.600 – 0.710]
IB
IEC Curve A
0.05
0.9
NA
1.5
0.860
[0.750 – 0.950]
5
0.214
[0.200 – 0.300]
51N
IC
IEEE Ext Inv
0.5
0.9
NA
1.5
11.34
[11.00 – 11.60]
5
0.648
[0.600 – 0.710]
51G
IG
Definite Time
2
0.9
NA
5
2.000
[1.900 – 2.100]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...