GEK-113285A
G650 Generator Protection & Control System
8-9
8 BOOTCODE AND FIRMWARE UPGRADE
8.3 FIRMWARE VERSION UPGRADE
8
8.3FIRMWARE VERSION UPGRADE
The relay settings and configuration will be lost, so it is advisable to save them to a file.
Take into account that if the
boot code has been previously upgraded, all the data (including calibration settings) was lost.
In case of error during the firmware upgrading process, the user could repeat the whole process as many times as
necessary, this is possible thanks to an independent boot memory (bootcode).
The firmware upgrading process should be done using the EnerVista 650 Setup software, after connecting the relay by
Ethernet port (COM3).
8.3.1 FIRMWARE UPGRADE
Once the communication with the relay through Ethernet connection has been verified
1
, enter the EnerVista 650 Setup
program, select
Communication
and the
Upgrade Firmware Version
option.
Therefore, it is necessary to save all settings to a file before following with the process.
Figure 8–16: FIRMWARE-BOOT VERSION COMPATIBILITY
After accepting to proceed, a window will open up for the upgrade parameter.t is also necessary to enter the ordering code
for the relay. See figure below:
1. Calibration settings should be stored in a file before upgrading the firmware.
Go to EnerVista 650 Setup main menu “
Communication > Calibration > Get Calibration Settings
”
Store the file in the PC using the relay serial number, for instance, as the name of the file.
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...