5-114
G650 Generator Protection & Control System
GEK-113285A
5.6 INPUTS/OUTPUTS
5 SETTINGS
5
d) WITH SIMPLE VOLTAGE SUPERVISION
Figure 5–32: SUPERVISION APPLICATION WITH AUXILIARY CONTACT 52A AND A RESISTOR (A6631F3)
Table 5–106: SUPERVISION WITH 52/A
There is a possibility to monitor the trip circuit and trip coil continuity. This can be done by monitoring Vdc through the
output contact when this is open.
INTERNAL STATE
V 52/A
SUPERVISION
52 open
ON
OK
52 closed
ON
OK
TRIP
OFF
OK if t < 0.5 s
TRIP with 52 open
OFF
OK if t < 0.5 s