GE Multilin
G60 Generator Protection System
B-11
APPENDIX B
B.4 MEMORY MAPPING
B
Digital Counter States Actual Values (Read Only Non-Volatile) (8 modules)
0800
Digital Counter 1 Value
-2147483647 to
2147483647
---
1
F004
0
0802
Digital Counter 1 Frozen
-2147483647 to
2147483647
---
1
F004
0
0804
Digital Counter 1 Frozen Time Stamp
0 to 4294967295
---
1
F050
0
0806
Digital Counter 1 Frozen Time Stamp us (microsecond part
of time stamp)
0 to 4294967295
---
1
F003
0
0808
...Repeated for Digital Counter 2
0810
...Repeated for Digital Counter 3
0818
...Repeated for Digital Counter 4
0820
...Repeated for Digital Counter 5
0828
...Repeated for Digital Counter 6
0830
...Repeated for Digital Counter 7
0838
...Repeated for Digital Counter 8
FlexStates (Read Only)
0900
FlexState Bits (16 items)
0 to 65535
---
1
F001
0
Element States (Read Only)
1000
Element Operate States (64 items)
0 to 65535
---
1
F502
0
User Displays Actuals (Read Only)
1080
Formatted user-definable displays (16 items)
---
---
---
F200
(none)
Modbus User Map Actuals (Read Only)
1200
User Map Values (256 items)
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14E0
Target Sequence
0 to 65535
---
1
F001
0
14E1
Number of Targets
0 to 65535
---
1
F001
0
Element Targets (Read/Write)
14E2
Target to Read
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14E3
Target Message
---
---
---
F200
“.”
Contact Input/Output States (Read Only)
1500
Contact Input States (6 items)
0 to 65535
---
1
F500
0
1508
Virtual Input States (8 items)
0 to 65535
---
1
F500
0
1510
Contact Output States (4 items)
0 to 65535
---
1
F500
0
1518
Contact Output Current States (4 items)
0 to 65535
---
1
F500
0
1520
Contact Output Voltage States (4 items)
0 to 65535
---
1
F500
0
1528
Virtual Output States (6 items)
0 to 65535
---
1
F500
0
1530
Contact Output Detectors (4 items)
0 to 65535
---
1
F500
0
Remote Input/Output States (Read Only)
1540
Remote Device States (2 items)
0 to 65535
---
1
F500
0
1542
Remote Input States (4 items)
0 to 65535
---
1
F500
0
1550
Remote Devices Online
0 to 1
---
1
F126
0 (No)
1551
Remote Double-Point Status Input 1 State
0 to 3
---
1
F605
3 (Bad)
1552
Remote Double-Point Status Input 2 State
0 to 3
---
1
F605
3 (Bad)
1553
Remote Double-Point Status Input 3 State
0 to 3
---
1
F605
3 (Bad)
1554
Remote Double-Point Status Input 4 State
0 to 3
---
1
F605
3 (Bad)
1555
Remote Double-Point Status Input 5 State
0 to 3
---
1
F605
3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0
Direct Input States (6 items)
0 to 65535
---
1
F500
0
15C8
Direct Outputs Average Message Return Time 1
0 to 65535
ms
1
F001
0
15C9
Direct Outputs Average Message Return Time 2
0 to 65535
ms
1
F001
0
15CA
Direct Inputs/Outputs Unreturned Message Count - Ch. 1
0 to 65535
---
1
F001
0
15CB
Direct Inputs/Outputs Unreturned Message Count - Ch. 2
0 to 65535
---
1
F001
0
15D0
Direct Device States
0 to 65535
---
1
F500
0
15D1
Reserved
0 to 65535
---
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 3 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...