6-20
G60 Generator Protection System
GE Multilin
6.3 METERING
6 ACTUAL VALUES
6
V
AB
and V
CB
are phase-to-phase voltage phasors
Î is the conjugate of I
g) ENERGY METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
ENERGY
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
).
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.
h) FREQUENCY METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
).
SOURCE FREQUENCY
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
POWER SYSTEM
settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
i) CURRENT HARMONICS AND THD METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
CURRENT HARMONICS
The metered current harmonics values are displayed in this menu. The "SRC 1" text will be replaced by whatever name
was programmed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
). Current
harmonics are measured for each source for the total harmonic distortion (THD) and 2nd to 25th harmonics per phase.
ENERGY
SRC 1
SRC 1 POS WATTHOUR:
0.000 Wh
MESSAGE
SRC 1 NEG WATTHOUR:
0.000 Wh
MESSAGE
SRC 1 POS VARHOUR:
0.000 varh
MESSAGE
SRC 1 NEG VARHOUR:
0.000 varh
FREQUENCY
SRC 1
SRC 1 FREQUENCY:
0.00 Hz
CURRENT HARMONICS
SRC 1
SRC 1
THD Ia: 0.0
Ib: 0.0
Ic: 0.0%
MESSAGE
SRC 1
2ND Ia: 0.0
Ib: 0.0
Ic: 0.0%
MESSAGE
SRC 1
3RD Ia: 0.0
Ib: 0.0
Ic: 0.0%
↓
MESSAGE
SRC 1 25TH Ia: 0.0
Ib: 0.0
Ic: 0.0%
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...