GE Multilin
G60 Generator Protection System
5-305
5 SETTINGS
5.8 INPUTS/OUTPUTS
5
DIRECT OUT 2 OPERAND:
"
HYB POTT TX1
"
DIRECT OUT 3 OPERAND:
"
DIRECT INPUT 5
" (forward a message from 1 to 3)
DIRECT OUT 4 OPERAND:
"
DIRECT INPUT 6
" (forward a message from 3 to 1)
Signal flow between the three IEDs is shown in the figure below:
Figure 5–164: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic and the resulting operand configured as the permission to trip (
HYB POTT RX1
setting).
5.8.11 TELEPROTECTION INPUTS AND OUTPUTS
a) OVERVIEW
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic operands to be sent via the selected communications channel. This allows the user to create distributed protec-
tion and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
TELEPROTECTION
TELEPROT INPUTS
TELEPROT INPUTS
TELEPROT INPUT 1-1
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 1-2
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
↓
MESSAGE
TELEPROT INPUT 1-16
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 2-1
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
MESSAGE
TELEPROT INPUT 2-2
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
↓
MESSAGE
TELEPROT INPUT 2-16
DEFAULT: Off
Range: Off, On, Latest/Off, Latest/On
842717A1.CDR
UR IED 3
UR IED 2
UR IED 1
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 5
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...