GE Multilin
G60 Generator Protection System
5-235
5 SETTINGS
5.6 GROUPED ELEMENTS
5
The element responds to the positive sequence impedance as shown below.
Figure 5–123: LOSS OF EXCITATION SCHEME LOGIC
5.6.15 ACCIDENTAL ENERGIZATION
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
ACCIDENTAL ENERGIZATION
ACCIDENTAL
ENERGIZATION
ACCDNT ENRG
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
ACCDNT ENRG SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
ACCDNT ENRG ARMING
MODE: UV and Offline
Range: UV and Offline, UV or Offline
MESSAGE
ACCDNT ENRG OC
PICKUP: 0.300 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
ACCDNT ENRG UV
PICKUP: 0.500 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
ACCDNT ENRG OFFLINE:
Off
Range: FlexLogic operand
MESSAGE
ACCDNT ENRG BLOCK:
Off
Range: FlexLogicoperand
MESSAGE
ACCDNT ENRG TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
ACCDNT ENRG EVENTS:
Disabled
Range: Disabled, Enabled
LOSS OF EXCITATION
FUNCTION:
LOSS EXCIT BLK:
SETTING
SETTING
Generator=1, Motor=1
Disabled=0
SETTING
Enabled=0
Disabled=1
LOSS OF EXCITATION
SOURCE:
SETTING
I_1
V_1
Off=0
830001AB.CDR
LOSS OF EXCITATION
CENTER 1:
LOSS OF EXCITATION
FUNCTION:
LOSS OF EXCITATION
CENTER 2:
LOSS OF EXCITATION
PKP DELAY 1:
LOSS OF EXCITATION
PKP DELAY 2:
LOSS OF EXCITATION
RADIUS 1:
LOSS OF EXCITATION
RADIUS 2:
RUN
RUN
OR
OR
SETTINGS
SETTING
SETTING
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
LOSS EXCIT STG1 PKP
LOSS EXCIT STG2 PKP
LOSS EXCIT STG1 DPO
LOSS EXCIT STG2 DPO
LOSS EXCIT STG1 OP
LOSS EXCIT STG2 OP
LOSS EXCIT OP
LOSS EXCIT PKP
LOSS EXCIT DPO
0 ms
20 ms
0 ms
0 ms
20 ms
0 ms
I_1 > 0.05 pu
BLOCK (See description)
RUN
COMPARATOR
RUN
SETTING
LOSS OF EXCITATION UV
SUPV 2 :
SETTING
Enabled=0
Disabled=1
LOSS OF EXCITATION
UV SUPV :
LOSS OF EXCITATION UV
SUPV 1 :
OR
OR
AND
|V_1| < PICKUP
AND
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...