GE Multilin
G60 Generator Protection System
5-233
5 SETTINGS
5.6 GROUPED ELEMENTS
5
The volts/hertz inverse C curves are shown below.
Figure 5–121: VOLTS-PER-HERTZ CURVES, INVERSE CURVE C
5.6.14 LOSS OF EXCITATION
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LOSS OF EXCITATION
LOSS OF
EXCITATION
LOSS OF EXCITATION
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LOSS OF EXCITATION
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
LOSS OF EXCITATION
CENTER 1: 10.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
LOSS OF EXCITATION
RADIUS 1: 8.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
EXCITATION V SUPV 1:
Enabled
Range: Disabled, Enabled
MESSAGE
LOSS OF EXCITATION
PKP DELAY1: 0.050 s
Range: 0.000 to 65.535 s in steps of 0.01
MESSAGE
LOSS OF EXCITATION
CENTER 2: 12.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
LOSS OF EXCITATION
RADIUS 2: 10.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
LOSS OF EXCITATION
V SUPV 2: Enabled
Range: Disabled, Enabled
MESSAGE
LOSS OF EXCITATION
PKP DELAY2: 0.500 s
Range: 0.000 to 65.535 s in steps of 0.01
MESSAGE
LOSS OF EXCITATION
UV SUPV: 0.700 pu
Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
LOSS OF EXCIT BLK:
Off
Range: FlexLogic operand
T
ime
to
trip
(i
n
seconds)
Multiples of volts per hertz pickup
830740A1.CDR
Time
delay
setting
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...