5-10
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
To gain write access to a “Restricted” setting, program the
ACCESS LEVEL
setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
If a remote connection is established, local passcodes are not visible.
REMOTE PASSWORDS
The remote password settings are visible only from a remote connection via the EnerVista UR Setup software.
Proper passwords are required to enable each command or setting level access.
To set the command or setting password:
1.
In the EnerVista software, navigate to
Settings > Product Setup > Security
menu item to open the remote password
settings window.
2.
Click the command or setting password
Change
button.
3.
Enter the new password in the
New Password
field. Requirements are outlined in the
Password Requirements
section
at the beginning of the chapter. When an original password has already been used, enter it in the
Enter Password
field and click the
Send Password to Device
button.
4.
Re-enter the password in the
Confirm Password
field.
5.
Click the
OK
button. The password is checked to ensure that is meets requirements.
If you establish a local connection to the relay (serial), you cannot view remote passcodes.
ACCESS SUPERVISION
PATH: SETTINGS
PRODUCT SETUP
SECURITY
ACCESS SUPERVISION
The following access supervision settings are available.
•
INVALID ATTEMPTS BEFORE LOCKOUT
: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the
LOCAL ACCESS DENIED
or
REMOTE ACCESS DENIED
FlexLogic operands are set to “On”. These operands are returned to the “Off” state upon
expiration of the lockout.
ACCESS
SUPERVISION
ACCESS LEVEL
TIMEOUTS
MESSAGE
INVALID ATTEMPTS
BEFORE LOCKOUT: 3
Range: 2 to 5 in steps of 1
MESSAGE
PASSWORD LOCKOUT
DURATION: 5 min
Range: 5 to 60 minutes in steps of 1
NOTE
NOTE
NOTE
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...