86
GE INFORMATION
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
CHAPTER 5: POWERING UP THE D400
The back panel contact closure indicator or audible alarm can be wired to operate as
follows:
•
Lit when a power failure has occurred
•
Lit when power is present
The Power Fail contact closure provides three contacts (terminals 1, 2 and 3) on terminal
block
TB2
.
Contact closure rated for 0.1 A @ 300 V maximum.
To connect the Power
Fail contact closure
1.
Remove the terminal block protective
plastic cover.
2.
Wire a lamp or audible alarm to terminals 1, 2 or 3 on terminal block
TB2
as follows
(see figure):
For proper connection, the recommended tool torque settings for power terminal
screws are 10.8 in-lb [1.22 Nm]. A Phillips (#1) screwdriver tip is recommended.
3.
Replace the terminal block protective plastic cover.
Figure 50: Power Fail Alarm Connection
System fail alarm
The D400 includes a System Fail contact closure to provide an external indication of
system status. The System Fail alarm is also indicated by the CPU Ready LED on the front
panel of the main module turning off.
The indicator or audible alarm can be wired to operate as follows:
•
ON when system failure has occurred
•
ON when system is functioning properly
To enable the indicator when power is…
Wire the lamp between…
Absent
Terminals 1 and 2
Present
Terminals 2 and 3
Station Battery / Power Source
Light ON
after failure
Light ON
when operational
Power
Fail
System
Fail
TB2
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...