38
GE INFORMATION
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
CHAPTER 3: SETTING UP COMMUNICATION CARDS
Switch SW1/SW2 configuration
Switches
SW1
(for Port 2) and
SW2
(for Port 1) control the signal type of the RS-232 port.
Each switch contains ten switch positions that can each be set to position
ON
or
OFF
to
select the appropriate port option.
Table 7: RS-232 Card Switch SW1/SW2 Settings
*Use DTE or DCE settings as appropriate
NOTE
DCD output is not supported in DCE mode.
NOTE
If configured with SW1/SW2, each +5 V is output on Pin 1 of rear DB9 connector and is
independently isolated and fused with a PTC (positive temperature coefficient) resettable
fuse at 320 mA at 65 °C.
Figure 10: Switch SW1/SW2 configuration for port DTE (default)
Figure 11: Switch SW1/SW2 configuration for port DCE
Port Option
SW1/SW2 Switch Position
1
2
3
4
5
6
7
8
9
10
DTE (default) - see Figure 10
ON
OFF ON
OFF ON
OFF ON
OFF ON
OFF
-
OFF OFF ON
OFF ON
OFF ON
OFF ON
+5 V (320 mA) isolated source
*
ON
*
*
*
*
*
*
*
*
ON
1
3
5
7
9
2
4
6
8
10
ON
1
4
6
8
10
2
3
5
7
9
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...