CHAPTER 2: INSTALLATION
ELECTRICAL INSTALLATION
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
2–31
Figure 2-34: Restricted Ground Fault Inputs
Zero-Sequence CT Installation
The figure below shows the various CT connections and the exact placement of a Zero
Sequence current CT, so that ground fault current can be detected. Twisted pair cabling on
the Zero Sequence CT is recommended.
Figure 2-35: Zero Sequence (Core Balance) CT Installation
J1 J2 J3 J4 J5 J6 J7 J8
CURRENT INPUTS
PHASE A PHASE B PHASE C GROUND
IA N
IC
IB
IG
N
N
N
FEEDER
TRANSFORMER
892775A1.cdr
Ground connection to neutral
must be on the source side
UNSHIELDED CABLE
LOAD
A
B
C
N
G
Ground
outside CT
Source
LOAD
SHIELDED CABLE
996630A5
A
B
C
Source
To ground;
must be on
load side
Stress cone
shields