CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
OUTPUTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
5–95
Outputs
Figure 5-33: Outputs Display Hierarchy
Output Relays
The 850 Feeder Protection System relay is equipped with a number of electromechanical
output relays specified at the time of ordering. The card A I/O module from slot F, for
example, provides five output relays.
The first output relay (Relay 1) in the 850 is a Form A relay that can be used for Trip Coil
monitoring, and is designated for tripping the breaker. The relay is energized upon
operation of any element with setpoint Function set to "Trip". The relay can be customized
by changing the name and type, and adding triggers or blocking, as shown in the Output
Relay setpoint descriptions. Output Relay 1 is programmed internally for tripping the
breaker, and it cannot be changed, disabled, or replaced by any other relay. Additional
output relays can be selected to operate as well from the menu of each protection, control,
or monitoring element.
Output Relay 2 is a Form A relay that can be used for Close Coil monitoring, and it is
selected as the default for closing the breaker. The 850 provides a selection of any
available output relay for closing the breaker under the Breaker > Close Relay Select
setpoint The output relay selected for closing the breaker can be triggered directly from
some relay functions designated to perform the breaker close action. If Relay 2 is not
selected as the Close relay, it can be used for other purposes. The "Trip" and "Close" relays
have fixed operating logic as they depend on breaker feedback for resetting.
The Trip and Close auxiliary relays follow the respective Trip and Close logic, meaning they
will have fixed operating characteristics as they depend on breaker feedback for resetting.
The auxiliary relays selected for breaker tripping are also available for selection from the
menus of all protection elements. The auxiliary relays selected for breaker closing are
excluded from the list for selection from the menu of all elements. Refer to the Breaker
setup section on how to select an auxiliary relay for breaker trip and close.
The operation of output relays selected for breaker Trip and breaker Close are breaker-
controlled relays designed to be controlled by the state of the breaker as monitored by a
52a contact, 52b contact, or both.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...