5–70
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Breakers
Breaker detection ON is performed on the 850 relay by monitoring the state/states of
either one, or preferably two, contact inputs. It is highly recommended to monitor the
status of the feeder breaker using both breaker auxiliary contacts 52a, and 52b. However
using only one of them is also acceptable. The 850-E and 850-D single feeder relays have
one controllable breaker. The 850-D dual feeder and 850-P relays have two controllable
breakers.
The breaker connection/disconnection to/from the power system (racked-out by the
breaker racking mechanism, or isolated by the associated disconnect switches on a fixed
circuit breaker) is provided by monitoring the contact input “BKR CONNECTED”. If the
contact input selected under the “BKR CONNECTED” setpoint is asserted, the breaker is
considered connected to the primary system. When the breaker is determined
disconnected, the breaker state is shown to be neither open, nor closed.
Path
:
Setpoints > System > Breakers > Breaker X
NAME
Range: Up to 13 alphanumeric characters
Default: BKR1
CONTACT INPUT 52a
Range: Off, Any FlexLogic operand
Default: Off
Selects the Contact Input connected to the breaker auxiliary contact 52a.
CONTACT INPUT 52b
Range: Off, Any FlexLogic operand
Default: Off
Selects the Contact Input connected to the breaker auxiliary contact 52b.
CONNECTED
Range: Off, Any FlexLogic operand
Default: Off
Select a contact input to show whether the breaker is connected (Racked-in, or
disconnect switches switched-on), or disconnected (racked-out, or disconnect switches
switched-off) from the system.
CLOSE RELAY SELECT
Range: Off, Relay 2
Default: Relay 2
FASTPATH:
If “Relay 2” is selected, Auxiliary Relay 2 is not available for selection in any element.
Table 5-9: Breaker status depending on availability of contacts 52a and 52b
52a Contact Configured
52b Contact Configured
Breaker Status
Open
Closed
Yes
Yes
52a contact open
52b contact closed
52a contact closed
52b contact open
Yes
No
52a contact open
52a contact closed
No
Yes
52b contact closed
52b contact open
No
No
Breaker Not Configured
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...