5–10
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Basic Security
The 8 Series Basic Security supports three roles: Administrator, Operator and Observer.
The Main Settings Structure is available from
Path:
Setpoints > Device > Security.
LOGIN
The setting allows a user to login with a specific role.
1.
Whenever a new role is logged in, the user is prompted to enter a password.
2.
If the wrong password is entered, an “Authentication Failed!” message is displayed
3.
If the maximum failed authentications occur an “Account Blocked!” message is
displayed.
4.
The Observer is the default choice and it does not require a password.
LOGOUT
This setting logs out the current user and logs in as Observer. If the user is already an
Observer, this setting does not apply. When logging out, a switch to Observer role is
performed.
CHANGE PASSWORDS
1.
The Change local passwords menu is shown on the front panel and EnerVista on a
successful login of Administrator role.
2.
If password complexity is enabled, the rules as defined in the Password Complexity
section must be obeyed. If password complexity is disabled this setting accepts 1 to
20 alphanumeric characters.
See
Path:
Setpoints > Device > Security > Change Local Passwords
.
3.
The default password is “0”, which is programmed from the factory.
4.
The “login setting” in this menu is similar to that in the parent security settings.
5.
The Observer does not have password associated with it. So there is no need to show
it in the list of password changing roles.
LOAD FACTORY DEFAULTS
The Administrator role can change this setting. This setting resets all the settings,
communication and Security passwords, and all records.
ACCESS LOCKOUT
Access lockout is the number of failed authentications (the default is 3 and the maximum is
99) before the device blocks subsequent authentication attempts for the lockout period. A
value of 0 shall mean Lockout is disabled.
ACCESS LOCKOUT PERIOD
Access lockout period is the period of time in minutes of a lockout (the default is 3 and the
maximum is 9999). A value of “0” means that there is no lockout period.
ACCESS TIMEOUT
Access timeout is the time of idleness before a logged in user is automatically logged out.
This timeout applies to all users, independent of the communication channel (serial,
Ethernet or direct access).
PASSWORD COMPLEXITY
This setting is available so that the option of selecting between simple passwords and
complex ones is provided.
•
The setting is only available to Administrator.
•
By default password complexity is disabled.
•
When password complexity is enabled, it follows the rules defined in the Password
Complexity section.
OPERATOR PIN PASSWORD
This setting allows a numeric password for the Operator even when Password Complexity
is enabled. When the Operator PIN password is enabled, a virtual numeric keypad is shown
instead of a virtual keyboard. By default, Operator PIN password is disabled. Changing this
setting changes the Operator password to the default “0”.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...