Upgrading Relay Firmware
To upgrade the 850 firmware, follow the procedures listed in this section. Upon successful
completion of this procedure, the 850 will have new firmware installed with the factory
default setpoints.The latest firmware files are available from the GE Grid Solutions website
at http://www.gegridsolutions.com.
FASTPATH:
EnerVista 8 Series Setup software prevents incompatible firmware from being loaded into
an 850 relay.
FASTPATH:
Note that uploading firmware on a Wi-Fi interface is not allowed.
Note that uploading firmware to a relay having a Communications card must be done
with “Port 4 operation” configured as independent.
FASTPATH:
Before upgrading firmware, it is very important to save the current 850 settings to a file on
your PC. After the firmware has been upgraded, it will be necessary to load this file back
into the 850. Refer to
Downloading and Saving Setpoints Files
for details on saving relay
setpoints to a file.
Loading New Relay
Firmware
Loading new firmware into the 850 flash memory is accomplished as follows:
1.
Connect the relay to the local PC and save the setpoints to a file as shown in
Downloading and Saving Setpoints Files
.
2.
Select the
Maintenance > Update Firmware
menu item. The following screen
appears. Select OK to proceed.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...