![GE Multilin 489 Instruction Manual Download Page 33](http://html.mh-extra.com/html/ge/multilin-489/multilin-489_instruction-manual_123013033.webp)
CHAPTER 2: INTRODUCTION
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–7
Accuracy:
...........................................................Fundamental
:+/-0.5% of Full Scale
3rd Harmonic at >3V secondary
: +/-5% of reading
3rd Harmonic at < 3V secondary
: +/- 0.15% of full scale
Max. continuous:
280 V AC
OUTPUT AND NEUTRAL END CURRENT INPUTS
CT primary:
10 to 50000 A
CT secondary:
1 A or 5 A (specify with order)
Conversion range:
0.02 to 20
×
CT
Accuracy:
at
<
2
×
CT: ±0.5% of 2
×
CT
at
≥
2
×
CT: ±1% of 20
×
CT
Burden:
Less than 0.2 VA at rated load
CT withstand:
1 s at 80
×
rated current
2 s at 40
×
rated current
continuous at 3
×
rated current
PHASE VOLTAGE INPUTS
VT ratio:
1.00 to 300.00:1 in steps of 0.01
VT secondary:
200 V AC (full-scale)
Conversion range:
0.02 to 1.00
×
full-scale
Accuracy:
±0.5% of full-scale
Max. continuous:
280 V AC
Burden:
>
500 K
Ω
RTD INPUTS
RTDs (3-wire type):
100
Ω
Platinum (DIN.43760)
100
Ω
Nickel, 120
Ω
Nickel,
10
Ω
Copper
RTD sensing current:
5 mA
Isolation:
36 Vpk (isolated with analog inputs and outputs)
Range:
–50 to +250°C
Accuracy:
±2°C/±4°F for Pt and Ni
±5°C/±9°F for Cu
Lead resistance:
25
Ω
max. per lead (Pt and Ni types); 3
Ω
max. per lead (Cu type)
NO sensor:
>
1 k
Ω
Short/low alarm:
<
–50°C
2.2.2
Outputs
ANALOG CURRENT OUTPUT
Type:
Active
Range:
4 to 20mA, 0 to 1 mA
(must be specified with order)
Accuracy:
±1% of full scale
4 to 20 mA max. load:
1.2 k
Ω
0 to 1 mA max. load:
10 k
Ω
Isolation:
36 Vpk (isolated with RTDs and analog inputs)
4 assignable outputs:
phase A, B, C output current, three-phase average current,
negative sequence current, generator load, hottest stator RTD,
hottest bearing RTD, RTDs 1 to 12, voltage (AB, BC, and CA),
average phase-phase voltage, volts/hertz, frequency, third
harmonic neutral voltage, power (3-phase Mvar, MW, and MVA),
power factor, analog inputs 1 to 4, tachometer, thermal
capacity used, demand (I, Mvar, MW, and MVA), torque