3. SETTINGS
24
MIV Digital Multifunctional Protective Relay
GEK-106271
COMMENTS ON THE SETTINGS:
GENERAL SETTINGS
1. GENERAL SETTINGS
1.1
RELAY STATUS:
This setting allows to put the unit out of service, so that it will not activate any output in any case, except for
the System Ready alarm, that will be active. The Ready LED on the front of the unit will remain red while the relay
is out of service.
1.2
IDENTIFICATION:
This setting allows to rename (20 characters) the unit in order to customize and identify it.
1.3
FREQUENCY:
This setting is the electrical system frequency: 50 or 60 Hz.
1.4
LINE VT RATIO:
This setting allows the user to view the line voltage measures (V3, V4 and V5) in primary. This setting does
not apply for the event record measures or the oscillography record, as these are shown in secondary.
1.5
V1 VT RATIO:
This setting allows the user to view the busbar voltage measure (V1) in primary. This setting does not apply
for the event record measures or the oscillography record, as these are shown in secondary.
1.6
V2 VT RATIO:
This setting allows the user to view the V2 voltage measure in primary. This setting does not apply for the
event record measures or the oscillography record, as these are shown in secondary.
1.7
ACTIVE TABLE:
This setting determines which particular settings are active, whether those of table 1, 2 or 3. When the
“ACTIVE TABLE” inputs are operative, they have priority over this setting, and therefore the setting can show a
different table than the one that is actually active, which will be determined by the corresponding inputs.
2. PERMISSIONSxFUNCTIONS
2.1
FUNCTION PERMISSION MASK:
With this Mask it is possible to enable or disable the operation of each function:
FUNCTION A, FUNCTION A’, FUNCTION B, FUNCTION C, FUNCTION D, FUNCTION E, FUNCTION F,
FUNCTION G, FUNCTION H, FUNCTION I and FUNCTION J.
Summary of Contents for MOV 2000
Page 3: ......
Page 7: ...TABLE OF CONTENTS 4 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Page 33: ...3 SETTINGS 30 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Page 37: ...4 TECHNICAL CHARACTERISTICS 34 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Page 41: ...5 HARDWARE DESCRIPTION 38 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Page 57: ...6 ACCEPTANCE TESTS 54 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Page 59: ...7 INSTALLATION AND MAINTENANCE 56 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Page 71: ...8 KEYPAD AND DISPLAY 68 MIV Digital Multifunctional Protective Relay GEK 106271 ...