7–14
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
Alter the following settings:
S2 SYSTEM SETUP
VOLTAGE SENSING
VT CONNECTION TYPE:
“Wye” or “Delta”
S2 SYSTEM SETUP
POWER SYSTEM
SYSTEM PHASE SEQUENCE:
“ABC”
S9 VOLTAGE ELEMENTS
PHASE REVERSAL
PHASE REVERSAL TRIP:
“Latched”
S9 VOLTAGE ELEMENTS
PHASE REVERSAL
ASSIGN TRIP RELAYS:
“Trip”
Apply voltages as per the table below.
Verify the 469 operation on voltage phase reversal.
7.3.5
Short Circuit Test
The 469 specification for short circuit timing is +50 ms. The pickup accuracy is as per the
phase current inputs. Perform the steps below to verify the performance of the short circuit
element.
Alter the following settings:
S2 SYSTEM SETUP
CURRENT SENSING
PHASE CT PRIMARY:
“1000”
S6 CURRENT ELEMENTS
SHORT CIRCUIT TRIP
SHORT CIRCUIT TRIP:
“On”
S6 CURRENT ELEMENTS
SHORT CIRCUIT TRIP
ASSIGN TRIP RELAYS:
“Trip”
S6 CURRENT ELEMENTS
SHORT CIRCUIT TRIP
SHORT CIRCUIT TRIP PICKUP:
“5.0
×
CT”
S6 CURRENT ELEMENTS
SHORT CIRCUIT TRIP
INTENTIONAL S/C DELAY:
“0”
Inject current as per the table below, resetting the unit after each trip
by pressing the
RESET
key, and verify timing accuracy.
Pre-trip values may be viewed by pressing
NEXT
after each trip.
APPLIED VOLTAGE
EXPECTED RESULT
8
NO TRIP
4
PHASE REVERSAL
TRIP
OBSERVED RESULT
8
NO TRIP
4
PHASE REVERSAL
TRIP
Va = 120 V
∠
0
°
Vb = 120 V
∠
120
°
Vc = 120 V
∠
240
°
8
Va = 120 V
∠
0
°
Vb = 120 V
∠
240
°
Vc = 120 V
∠
120
°
4
INJECTED CURRENT
EXPECTED TIME
TO TRIP
MEASURED TIME
TO TRIP
5 A UNIT
1 A UNIT
30 A
6 A
< 50 ms
40 A
8 A
< 50 ms
50 A
10 A
< 50 ms
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...